Table 3: Service Supply Wiring Sizes
Recommended Minimum supply wire sizes are listed in the table
below:
1. Wire all heaters and controls in accordance with the appropri-
ate wiring diagram provided on page 4.
2. Run a ground jumper from the ground screw in one terminal
box to the ground screw in the adjacent terminal box. (See
Figure 4.)
Table 4: Terminal Box Volumes (Cubic Inches)
3. Do a final and complete check of all wiring, then replace the
terminal box covers being careful not to pinch any wires.
4. The front/top panel may now be installed.
WARNING: To prevent the risk of fire, do not oper-
ate the heater without the front/top panels in place.
5. Place the front panel over the flange of the bottom panel. Hook
the top back edge of the front panel over the back panel, and
snap onto the plastic clips.
Maximum Watts Per Circuit Using 75 Degree C. Wire
Rough In
Wire Size
120V
208V
240V
277V
347V
480V
600V
14
1440
2496
2880
3324
4164
5760
7200
Copper
12
1920
3328
3840
4432
5552
7680
9600
Wire
10
2880
4992
5760
6648
8328
11520
14400
Heater Style
Left Hand Box
Right Hand Box
4” Wide
5” Wide
CAF-6, CCAS-8
33.25
41.50
WIRING
WIRING DIAGRAMS
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.