Fan blaDe settInGs
Shown in Figure 8 are the correct fan blade setting 
dimensions for proper air delivery across the outdoor 
coil.
Any service work requiring removal or adjustment 
in the fan and/or motor area will require that the 
dimensions below be checked and blade adjusted in or 
out on the motor shaft accordingly.
MD-1417BC
serVIce anD trOubleshOOtInG
serVIce hInts
1.  Caution homeowner to maintain clean air filters at 
all times.  Also, not to needlessly close off supply 
and return air registers.  This reduces airflow 
through the system which shortens equipment 
service life as well as increasing operating costs.
2.  Check all power fuses or circuit breakers to be sure 
that they are the correct rating.
3.  Periodic cleaning of the outdoor coil to permit full 
and unrestricted airflow circulation is essential.
Pressure serVIce POrts
High and low pressure service ports are installed on 
all units so that the system operating pressures can be 
observed.  Pressure tables can be found later in this 
manual covering all models on cooling cycle.  It is 
imperative to match the correct pressure table to the 
unit by model number.
r-410a
reFrIGerant charGe
This unit was charged at the factory with the quantity 
of refrigerant listed on the serial plate.  AHRI capacity 
and efficiency ratings were determined by testing with 
this refrigerant charge quantity.
The following pressure tables show nominal 
pressures for the units.  Since many installation 
specific situations can affect the pressure readings, 
this information should only be used by certified 
technicians as a guide for evaluating proper system 
performance.  They shall not be used to adjust charge.  
If charge is in doubt, reclaim, evacuate and recharge 
the unit to the serial plate charge.
table  8
InDOOr blOWer PerFOrmance 
1  Motor will deliver consistent CFM through voltage supply range with no deterioration
  (197-253V for all 230/208V models).
2  Continuous CFM is the total air being circulated during continuous (manual fan) mode.
3  Will occur automatically with a call for “Y” for cooling mode operation.
4  Will occur automatically with a call for “W1” for heating mode operation.
FIGure  8
Fan blaDe settInG
model
rated
esP
max
esP
continuous 
Airflow
rated
cooling cFm
m
rated
heating cFm
PA1324
0.10
0.50
600
800
800
PA1330
0.15
0.50
750
1000
1000
PA1336
0.15
0.50
825
1100
1100
PA1342
0.20
0.50
925
1400
1400
PA1348
0.20
0.50
1025
1550
1550
PA1360
0.20
0.50
1150
1750
1750
3¼"