Bard PA13602-B Manual De Usuario

Descargar
Página de 24
Manual 2100-467K 
Page 
13 of 24
FIGure  5
cOnDensate DraIn traP
5. 
Other InstallatIOns  
– Many other 
installations are possible with the packaged air 
conditioner.  No matter what the installation, always 
consider the following facts:
 
A.  Insure that the discharge air is not obstructed in  
  any way so as to cause operation difficulties.
 
B.  The indoor coil drain pan is equipped with a   
 
coupling that must be piped through a  
 
 
condensate drain trap to a suitable drain.
 
C.  Always mount the unit is such a position that it  
 
may be easily reached for servicing and  
 
 maintenance.
 
D.  Insure that the unit is clear so that proper air   
  flow over the outdoor coil will be maintained.  
If this unit is operated in cooling below a 55° outdoor 
ambient temperature, the installation of low ambient 
controls (CMA-28) to unit is required.
cOnDensate DraIn traP
It is very important to provide a trap in the condensate 
drain line to allow a positive liquid seal in the line and 
assure correct drainage from the coil condensate pan.
Install condensate drain trap shown in Figure 8.  Use 
drain connection size or larger.  Do not operate unit 
without trap.  Unit must be level or slightly inclined 
toward drain.  With a trap installed on a unit located in 
an unconditioned area, water in the trap may freeze.  It 
is recommended that the trap material be of a type that 
will allow for expansion of water when it freezes.
aIr FIlters
Air filters for the return air side of the system are not 
provided as part of these models, and must be field 
supplied and installed as part of the final installation.  
Prior thought should be given to return air location and 
placement of the air filter(s).  The air filter(s) must be 
of adequate size and readily accessible to the operator 
of the equipment.  Filters must be adequate in size and 
properly maintained for proper operation.  If this is 
not done, excessive energy use, poor performance, and 
multiple service problems will result.  It is impossible 
to oversize air filters.  Generous sizing will result in 
cleaner air and coils as well as lower operating costs 
and extend the time between required changes.  Table 
5 shows minimum filter areas and recommended filter 
sizes.  Actual filter sizes can vary with the installation 
due to single or multiple returns utilizing a filter/grille 
arrangement or being placed immediately ahead of the 
indoor coil face in the return air duct.
NOTE:  If roof hood accessory is to be used, 
information on air filters may be found under 
that heading in this manual.  Air filters are 
supplied as part of that package.
table  5
FIlter requIrements & sIzes
model no.
minimum Filter
Free area
minimum
recommended size
PA1324
PA1330
PA1336
403 Square  Inches
(2.8 Square Feet)
(2) 14 x 20 x 1
PA1342
PA1348
PA1360
473 Square Inches
(3.3 Square Feet)
(2) 16 x 20 x 1