MAC2000 
Operation 
Note:
  The MAC2000 will automatically restart the recovery process 
if the unit senses a rise in the A/C system’s pressure. 
 
5. 
After recovering the refrigerant from the A/C system, close the 
service-port valves, and then remove the hoses from the vehicle. 
 
Observe that the service hoses should remain under vacuum. This 
ensures that no contaminants are introduced into the A/C system 
during a recharge process. 
 
6. 
The technician can now begin repairs on the A/C system. 
 
 
3.4  Vacuum Mode (Evacuation) 
 
The Vacuum mode is used to remove residual air and moisture from 
the vehicle’s A/C system by pulling the system into a deep vacuum. 
This mode is most often used after completing a repair that required 
opening the A/C system to the atmosphere. Moisture and/or air in an 
A/C system can cause erratic operation and must be removed before 
recharging the system with refrigerant.   
 
Evacuate a vehicle’s A/C system as follows: 
 
1. 
If not already done, plug the MAC2000 into a properly grounded 
AC outlet; set the Power switch to ON; then wait until the unit 
completes its self diagnostics. The screen will display “Select 
mode
” when ready. 
 
2. 
Connect the high- and low-side service hoses to their respective 
service ports on the vehicle’s A/C system; then open the A/C 
system’s service-port valves. 
 
3. 
Press the Vacuum mode function key and observe that the screen 
reads “Set VACUUM TIME now.” The minimum evacuation time 
is 3 minutes. To change this time, press and hold the Increase key 
until the desired time is shown. 
 
4. 
Press the Start key to begin the evacuation process.  
 
Note:  
Before evacuation begins, the MAC2000 checks if pressure is 
present in the vehicle. If pressure is sensed, the unit will display the 
message: “Error: You have pressure in the hoses. You must 
first recover this refrigerant before proceeding
.” If this error 
message appears, first abort the evacuation process by pressing the 
Reset
 key, recover the system per Section 3.3, then restart the 
evacuation process by pressing the Vacuum mode function key. 
 
5. 
The evacuation process continues for the amount of time set in 
Step 3. If a vacuum level of at least 27 inHg is not achieved within 
the prescribed time, the evacuation process automatically 
continues for a maximum of 7 minutes, or until 27 inHg is 
Instruction 2072-0400 