Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
valve shall be tested for leaks. 
 
1.4.9 V
ENTING 
O
G
AS 
T
RAIN 
C
OMPONENTS
 
 
Figure 2 Main Gas Inlet Connection 
 
 
Normally open vent valves (when supplied) - 
These valves must be piped to outdoors using 
pipe no smaller than that of the valve. 
 
Gas pressure switches – All gas pressure 
switches provided are of the VENTLESS type 
and do not require venting to atmosphere.   
 
Gas pilot pressure regulator – A vent limiter for 
the pilot pressure regulator is provided 
eliminating the need to run a vent line to 
atmosphere. 
NOTE: 
Do not use Teflon tape for threaded joints in gas 
piping. 
1.5 E
LECTRICAL 
R
EQUIREMENTS
 
WARNING: 
All electrical connections must 
conform to the National Electrical 
Code and to all other applicable State 
and Local Codes.  See boiler wiring 
diagram and equipment list for specific 
voltage requirements. 
Model TF300/250 
TF200/150 
200 V – 240 V / 60 Hz / 3 Ph 
Blower Motor 
KW (HP) 
3 (4.02) 
N/A 
Full Load 
15.6 N/A 
Service Fuse 
(3) 20 Amp 
N/A 
400 V – 480V / 60 Hz / 3 Ph 
Blower Motor 
KW (HP) 
N/A N/A 
Full Load 
Amps
1
N/A N/A 
Service Fuse 
N/A 
N/A 
200 V – 240 V / 60 Hz / 1 Ph 
Blower Motor 
KW (HP) 
N/A 1.05 
(1.41) 
Full Load 
Amps
1
N/A 6 
Service Fuse 
N/A 
(2) 7 Amp 
Table 2 Electrical Requirements 
 
Equipment Grounding  
The boiler must be grounded in accordance with 
the current American National Standard 
Electrical Code, ANSI/NFPA #70. 
1.6 C
OMBUSTION 
A
IR 
S
UPPLY
 
Combustion Air: 
For proper combustion it is necessary to provide 
the boiler room with appropriate openings for 
fresh air supply.  Temporary air intakes such as 
windows and doors should be avoided since 
they may be closed.  In addition to air needed 
for combustion, sufficient air must be supplied 
for ventilation as well as other air consuming 
equipment that may be present in the boiler 
room.  Often when personnel are working in the 
boiler room, combustion air openings are closed 
due to the temperature of the outside air.  THIS 
MUST BE AVOIDED AT ALL COSTS! 
 
Provisions should be made to heat the outside 
combustion air, if necessary, for personnel 
comfort. 
 
Positive means for supplying an ample amount 
of outside air, allowing for the complete 
combustion of the gas, must be provided. 
 
Movable combustion air dampers, automatic or 
manually adjustable, must be electrically 
                                                      
 
1
  Full load Amps include blower and control 
circuit.