SECTION 3. 
Gas Supply and Piping
3.1  Gas Supply and Piping
Gas piping should be supported by suitable 
hangers or floor stands, not by the appliance.
The Brute Deluxe’s gas train allows the user to 
pipe the gas from either the right side or the left side 
of the unit. As shipped, the right side of the gas train is 
capped off, and there is a manual valve on the left side. 
If desired, the manual valve on the left side of the gas 
train may be moved to the right side, and the cap on 
the right side may be moved to the left. 
Review the following instructions before 
proceeding with the installation.
1.  Verify that the appliance is fitted for the proper 
type of gas by checking the rating plate. Brute 
Deluxe appliances are equipped to operate at 
elevations up to 10,000 feet (3050m). Brute 
Deluxe appliances may be adjusted to operate 
properly at altitudes above 2500 feet (see Section 
6.5.2) and the input will be reduced if the heating 
value of the gas supply is below sea level values.
2.  The maximum inlet gas pressure must not 
exceed 13" w.c. (3.2kPa). The minimum inlet gas 
pressure is 5 in. w.c. (1.2 kPa).
3.  Refer to 
Table 7
, size supply.
4.  Run gas supply line in accordance with all 
applicable codes.
5.  Locate and install manual shutoff valves in 
accordance with state and local requirements.
6.  A sediment trap must be provided upstream of 
the gas controls.
7.  All threaded joints should be coated with 
piping compound resistant to action of liquefied 
petroleum gas.
8.  The appliance and its individual shutoff valve 
must be disconnected from the gas supply piping 
during any pressure testing of that system at test 
pressures in excess of 0.5 psig (3.45 kpa).
9.  The unit must be isolated from the gas supply 
system by closing its individual manual shutoff 
valve during any pressure testing of the gas 
supply piping system at test pressures equal to or 
less than 0.5 psig (3.45 kpa).
10.  The appliance and its gas connection must be 
leak tested before placing it in operation.
11.  Purge all air from gas lines.
   WARNING
Do not use open flame to check for leaks. An open 
flame could lead to explosion, which could result in 
property damage, serious injury or death.
   AVERTISSEMENT
Ne recherchez pas les fuites avec une flamme nue. 
Une flamme nue peut provoquer une explosion qui 
peut causer des dommages matériels, de sérieuses 
blessures corporelles ou la mort.
NOTE: The Brute Deluxe appliance and all other 
gas appliances sharing the gas supply line must 
be firing at maximum capacity to properly measure 
the inlet supply pressure. The pressure can be 
measured at the supply pressure port on the gas 
valve. Low gas pressure could be an indication of 
an undersized gas meter, undersized gas supply 
lines and/or an obstructed gas supply line.
Distance from Gas Meter or Last Stage Regulator
Size and
Gas Type
0-100'
0-31 m
100-200'
31-61m
200-300'
61-91m
200 natural
1¼"
3.2 cm
1¼"
3.2 cm
1¼"
3.2 cm
200 propane
1"
2.5 cm
1"
2.5 cm
1¼"
3.2 cm
300 natural
1¼"
3.2 cm
1½"
4.0 cm
1½"
4.0 cm
300 propane
1
2.5 cm
1¼"
3.2 cm
1¼"
3.2 cm
400 natural
1¼"
3.2 cm
1½"
4.0 cm
2"
5.0 cm
400 propane
1¼"
3.2 cm
1¼"
3.2 cm
1½"
4.0 cm
Notes:
1.  These figures are based on 1/2" (0.12 kPa) water column pressure drop.
2.  Check supply pressure and local code requirements before proceeding with work.
3.  Pipe fittings must be considered when determining gas pipe sizing
.
Table 7. Gas Piping Size.