IMPORTANT: The inlet gas pressure to the appliance 
must not exceed 13 in. w.c. (3.2 kPa).
All installations must be made in accordance with:
1) In the U.S., the " National Fuel Gas Code "ANSI 
Z223.1/NFPA54, Latest Edition and all applicable 
local codes as required by the Authorities Having 
Jurisdiction (AHJ), or 
2) In Canada, the "Natural Gas and Propane 
Installation Code", CSA B149.1, latest edition and all 
applicable local codes as required by the AHJ. 
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code" (NEC), 
ANSI/NFPA 70, latest Edition and all applicable local 
codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code - Part 
1”, CSA STD. C22.1 and all applicable local codes as 
required by the AHJ. 
This appliance must be electrically grounded in 
accordance with the applicable codes and standards 
referenced above.
1.2  Model Identification
Consult the rating plate on the unit. The 
following information describes the model number 
structure.
Model Character Designation
1-3  Model Series Designation
 
B  M  T  2 = Brute Deluxe
4  Usage
 
H = Hydronic
 
V = Volume Water
5-8  Size
 
0  2  0  0 = 199,900 BTU/h input
 
0  3  0  0 = 299,000 BTU/h input
 
0  4  0  0 = 399,900 BTU/h input
9  Fuel
 
N = Natural Gas
 
P = Propane
10  Altitude
 
A = 0-5000 feet
 
H = over 5000 feet
11  Location
 
C = Indoor and Outdoor
12  Firing Mode
 
C = On-Off 
(standard)
 
K = Two-stage 
(optional)
13  Revision
 
1 = Revision Level 1
14  Heat Exchanger
 
B = Glass-lined CI / copper / brz trim 
(std. BMT2V)
 
C = Glass-lined cast iron / copper 
(std. BMT2H)
 
N = Glass-lined cast iron / cu-nickel 
(BMT2H)
 
 
P = Glass-lined cast iron / cu-nickel / brz trim
 (BMT2V)
 
2 = Glass-lined cast iron / copper, brz trim, HLW
 
5 = Glass-lined cast iron / cu-nickel / brz, HLW
15  Options Code
 
X = Standard unit
16  Pump Options
 
X = No Pump
1.3  Warranty
Bradford White's Brute Deluxe appliances are 
covered by a limited warranty. The owner should 
fill out the warranty registration card and return it to 
Bradford White.
All warranty claims must be made to an 
authorized Bradford White representative or directly 
to the factory. Claims must include the serial number 
and model (this information can be found on the rating 
plate), installation date, and name of the installer. 
Shipping costs are not included in the warranty 
coverage.
Some accessory items are shipped in separate 
packages. Verify receipt of all packages listed on 
the packing slip. Inspect everything for damage 
immediately upon delivery, and advise the carrier of 
any shortages or damage. Any such claims should be 
filed with the carrier. The carrier, not the shipper, is 
responsible for shortages and damage to the shipment 
whether visible or concealed.
1.4  Dimensions
See Figures 1A and 1B.
1.5  Locating the Appliance
The appliance should be located to provide 
clearances on all sides for maintenance and inspection. 
It should not be located in an area where leakage of 
any connections will result in damage to the area 
adjacent to the appliance or to lower floors of the 
structure.
When such a location is not available, it is 
recommended that a suitable drain pan, adequately 
drained, be installed under the appliance. 
The appliance is design certified by CSA-
International for installation on combustible flooring; 
in basements; in closets, utility rooms or alcoves
Brute Deluxe Boilers or Water Heaters must never 
be installed on carpeting. The location for the 
appliance should be chosen with regard to the vent 
pipe lengths and external plumbing. The unit shall be 
installed such that the gas ignition system components 
are protected from water (dripping, spraying, rain, etc.) 
during operation and service (circulator replacement, 
control replacement, etc.). When vented vertically, the 
Brute Deluxe must be located as close as practical to 
a chimney or outside wall. If the vent terminal and/
or combustion air terminal terminate through a wall, 
and there is potential for snow accumulation in the 
local area, both terminals should be installed at an 
appropriate level above grade such that blockage of 
the terminal from accumulated debris or precipitation 
is prevented.