The dimensions and requirements that are shown 
in 
Table 2 
should be met when choosing the locations 
for the appliance.
 
1.6  Locating Pump-Mounted Water Heater 
with Respect to Storage Tank(s)
For best results, a pump-mounted Brute Deluxe 
water heater should be located within 15 feet (4.6m) 
of the storage tank(s). The pump is sized for 30 feet 
(9.1m) of piping.
If the appliance must be installed with longer 
piping runs, then larger diameter pipe or tubing may be 
acceptable. Consult the factory for assistance.
1.7  Locating Pump-Mounted Boiler with 
Respect to Return/Supply Header
For the best results, a pump-mounted Brute 
Deluxe boiler should be located within 15 feet (4.6m) 
of the supply and return headers. The pump is sized for 
30 feet (9.1m) of piping.
If the appliance must be installed with longer 
piping runs, then larger diameter tubing may be 
acceptable. Consult the factory for assistance.
Size
Vent Collar
Size
Horizontal
Vent Pipe
Diameter
Intake
Air Collar
& Pipe
Diameter
Max. Pipe
Length
Max. No.
of Elbows
Side Vent
Terminal
Part Number
Side Wall
Combustion
Air Terminal
Part Number
in
cm
in
cm
in
cm
ft
m
200
5
13
4
10
4
10
50
15
3
CA003101
CA003201
300
6
15
5
13
4
10
50
15
3
CA003102
CA003201
400
7
18
6
15
6
15
50
15
3
CA003103
CA003202
 
 
 
Table 1.  Horizontal Vent / Combustion Air Parameters.
Appliance
Surface
Required
Clearance From
Combustible Material
Recommended
Service Access
Clearance
inches
cm
inches
cm
Left Side
1
2.5
24
61
Right Side
1
2.5
24
61
Top
1
2.5
12
30
Back
1
2.5
12**
30**
Front
1
2.5
36
91
Vertical
(Category 1) 
Vent
6*
15.2*
Horizontal 
(Category 3) 
Vent
per UL 1738 venting 
system supplier's 
instructions
*1" (2.5 cm) when b-vent is used.
**When vent and/or combustion air connects to the back, 
recommended clearance is 36" (91cm).
Table 2. Clearances.
1.8  Locating Appliance for Correct 
Horizontal Vent/Ducted Air Distance 
From Outside Wall
The forced draft combustion air blower in the 
appliance has sufficient power to pull air and vent 
properly when the guidelines for horizontal air and 
vent are followed (
see Table 1
).
NOTE: On some models, the vent collar size is 
larger than the size of the vent pipe that can be 
used. Vent collar size and horizontal pipe diameters 
can be found in 
Table 1.
 The larger vent collar 
size is to accommodate Category I (vertical) vent 
systems.
NOTE: When located on the same wall, the Brute 
Deluxe combustion air intake terminal must be 
installed a minimum of 12" (30cm) below the 
exhaust vent terminal and separated by a minimum 
of 36 inches (91cm) horizontally.
The air intake terminal must be installed high 
enough to avoid blockage from snow, leaves and other 
debris.