Bradford-White Corp BRHHV Manual De Usuario

Descargar
Página de 56
 
B
RADFORD
 W
HITE
 C
ORP.
Page 44
6. 
When the call for heat is complete, or the unit 
reaches its setpoint temperature, the gas valve 
will close, and the fan will continue to run for 
its 30 second post-purge. If a pump time delay 
is used, the pump will continue to run for the 
specified amount of time (adjustable from 0.1 to 
10 minutes).
8.2 Resolving Lockouts
There are many causes of lockouts. The four 
most common causes are: (1)  inadequate gas supply, 
(2) poor combustion, (3) ignitor failure (4) combustion 
air.
1. 
Inadequate gas supply: Before proceeding, ensure 
that the gas supply has not been shutoff or the LP 
tank (LP boilers) is not empty. Then, restart the 
boiler and observe the operational cycle. After 
the pre-purge time, the unit should light. If it 
does not, consult the factory.
2. 
Poor Combustion: Poor combustion should be 
suspected if there is a strong flue gas odor. The 
odor may result from an improper gas/air ratio 
(high or low O
2
 or CO
2
). If an improper gas/air 
ratio is suspected, consult the factory.
3. 
Ignitor failure: If the boiler goes through a 
normal start cycle but combustion does not 
occur, ignitor failure should be suspected. Check 
the ignitor by unplugging the ignitor plug and 
measuring the ignitor resistance. It should be 
50-80 (Ω) ohms. If the resistance is not 50-80 
ohms (Ω), replace the ignitor. If the resistance is 
correct, reset the boiler and check for 120 VAC 
at the ignitor plug during the start cycle. If there 
is no voltage, replace the faulty ignitor wire 
harness.
4. 
Inadequate combustion air:  If the boiler goes 
through a normal ignition cycle, and shuts off 
after the blower ramps up to full speed, an 
abnormal restriction in the air intake or exhaust 
system should be suspected.  Check the air filter 
for buildup of debris and clean filter if necessary. 
Inspect all exhaust venting and intake venting for 
blockages.  Remove any blockages and inspect 
and replace any damaged vent sections.  If the 
unit still continues to lockout after igniting, 
consult the factory.
Once the reason for the lockout has been 
identified and resolved you can reset the unit by 
pressing the manual reset button (see Detail A in 
Figure 30, Control Panel).
8.3  Delayed Ignition - Possible Causes
8.3.1  High Lockup Pressure (LP Appliances) 
- Occurs on Start-up
High lock up pressure is the most common 
cause of delayed ignitions on LP fueled appliances. It 
may result from an improper second stage regulator 
selection or from a faulty regulator.
Lock up can be detected by measuring the gas 
supply pressure to the appliance at the inlet pressure 
port on the gas valve. The gas supply to the appliance 
must be shut off before making any connections. 
To check: use a water manometer or pressure gauge 
with a scale reading of at least 25 in. W.C. or 15 oz/
in
2
. (6.2kPa). Attach the manometer to the gas valve 
inlet pressure port. Turn on the gas supply. The 
Brute Magnum appliance is designed to operate with 
supply pressures of 4-13 in. W.C. (2.3 - 7.5 oz/ in²) 
(1.0-3.2kPa). If the supply pressure exceeds 13 in. 
W.C. (7.5 oz/ in²) (3.2kPa) (with the appliance off) it 
is possible that this may be the cause of the delayed 
ignitions and the inlet pressure must be reset to 
between 4-13 in. W.C. (2.3 – 7.5 oz/in
2
) (0.1-3.2kPa). 
Restart the appliance and then switch it off. If the inlet 
gas pressure exceeds 13 in. W.C. (7.5 oz/ in²) (3.2kPa) 
after the appliance is switched off, correct the lock up 
problem.
8.3.2  Gas Valve Regulation 
Gas valve regulation problems can also cause 
delayed ignitions. If gas valve regulation problems are 
suspected, consult the factory. Do not attempt field 
adjustment or repair.
8.3.3  Defective Burner - Occurs on Startup 
or at Burner Shutdown
A defective burner can cause a delayed ignition. 
If the gas supply pressure is proper, and the gas valve 
is functioning properly, the burner should be inspected. 
There should be no distortion or perforations in the 
burner. Replace if indicated.
8.4  Short Cycling — Boiler
Because the Brute Magnum is a modulating 
boiler, and its input will decrease when there is a 
reduction in heating load, short cycling is greatly 
reduced. If the heating load drops below the minimum 
input of the boiler for an extended period, the boiler 
will have a tendency to short cycle. This can be a 
symptom of improper control strategy or setpoints, or 
a load distribution problem. See Section 5.5 regarding 
controller setup. Contact your Representative to 
discuss possible remedies.