6.8  To Restart the Brute Deluxe
If drained, follow 
Section 6.1
 in this manual for 
proper filling and purging.
1.  Switch off the main electrical disconnect switch.
2.  Close all manual gas valves.
3.  WAIT FIVE (5) MINUTES.
4.  Set the aquastat or thermostat to its lowest 
setting.
5.  Open all manual gas valves.
6.  Reset all safety switches (pressure switch, 
manual reset high limit, etc.).
7.  Set the temperature controller to the desired 
temperature setting and switch on electrical 
power.
8.  Burner will go through a pre-purge period and 
ignitor warm-up period, followed by ignition.
SECTION 7.
Maintenance
7.1  System Maintenance
1.  Lubricate the system water-circulating pump, if 
required, per the instructions on the pump. 
2.  If a strainer is employed in a pressure reducing 
valve or the piping, clean it every six months.
3.  Inspect the venting system for obstruction or 
leakage at least once a year. Periodically clean 
the screens in the vent terminal and combustion 
air terminal (when used).
4.  Keep the appliance area clear and free from 
combustible materials, gasoline, and other 
flammable vapors and liquids.
5.  If the appliance is not going to be used for 
extended periods in locations where freezing 
normally occurs, it should be isolated from the 
system and completely drained of all water. All 
systems connected to it should also be drained or 
protected from freezing.
6.  Low water cutoffs, if installed, should be 
checked every 6 months. Float type low water 
cutoff should be flushed periodically.
7.  Inspect flue passages, and clean with brushes/
vacuums, if necessary. Sooting in flue passages 
indicates improper combustion. Determine the 
cause and correct.
8.  Inspect the vent system and air intake system, 
and if the vent system is Category III, ensure 
that all joints are sealed properly. If joints need 
to be resealed, follow venting manufacturer's 
instructions to clean and reseal vent system. 
7.2  Appliance Maintenance and 
Component Description
Only genuine Bradford White replacement parts should 
be used.
 Caution
Label all wires prior to disconnection when servicing 
controls. Wiring errors can cause improper and 
dangerous operation. Verify proper operation after 
servicing.
 Attention
Lors d’entretien ou de réparation des commandes, 
étiquetez tous les câbles avant de les déconnecter. 
Des erreurs de câblage peuvent provoquer des 
fonctionnements incorrects et dangereux. Après 
toute intervention d’entretien ou de réparation, 
vérifier que l’appareil fonctionne correctement.
The gas and electric controls on the appliance 
are engineered for long life and dependable operation, 
but the safety of the equipment depends on their