Honeywell L7224 Manual De Usuario

Descargar
Página de 4
3
69-1957—1
L7224 SERIES
Table 2. L7224 Controller Operating Sequence
Troubleshooting
When attempting to diagnose system performance, reference the 
LED display to help identify specific areas not working properly. 
The LED display will scroll “err”, followed by a digit (1-8). See 
Table 1 for a description of the error and suggested actions. See 
below for a troubleshooting guide.
Action
System Response
Thermostat 
calls for heat.
Circulator starts when water temperature is 
above Low Limit setting (if applicable). Boiler 
temperature is checked. Burner starts when 
water temperature is below High Limit setting.
Boiler exceeds 
the High Limit.
Burner is turned off. Burner restarts when the 
water temperature drops below the High Limit 
setting minus the differential. 
Thermostat is 
satisfied.
Circulator and burner turn off.
Error conditions 
1-5.
If an error condition is detected, all outputs 
except ZC are shut down. Burner is off. Control 
continues to function and restarts when error is 
corrected. During the error check sequence, the 
system checks for drift in the sensor and 
corrosion in the connections.
Error conditions 
6-7.
If error condition 6 or 7 occurs, the control has 
reset the High Limit, Low Limit and Differential 
Setting to a default setting and will continue to 
run at those settings. Performance of the system 
will be degraded.
Error condition 
8.
If the error condition is detected, all outputs 
except ZC are shut down. Burner is off. Control 
continues to function and restarts when all three 
user keys have been pressed longer than 60 
seconds.
Table 3. Troubleshooting Guide
a
.
System 
Condition
Diagnostic 
Condition
Check
Action
Boiler is 
cold, 
house is 
cold 
Display is OFF 120 Vac system 
power.
Turn system power on.
Display is ON; 
TT-LED is OFF
24 Vac T-T
No 24V; replace 
control
Display is ON; 
TT-LED is OFF
24V present; 
disconnect 
thermostat, 
short T-T
Boiler starts, check 
wiring and thermostat
a
. Refer to Fig. 5 for Display and LED locations.
b
. ZC LED ON indicates ZC terminal power is OFF.
c
. ZC LED OFF indicates ZC terminal power is ON.
69-1957-1.fm  Page 3  Tuesday, June 20, 2006  11:06 AM