S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
16
Fig. 22. Safety parameter confirmation.
Press the Yes button to confirm each safety parameter block. If 
the No button is selected, the safety parameter block remains 
unconfirmed and the Configuration menu page is displayed. 
The control remains in an unconfigured state in this case.
After all safety parameter blocks have been confirmed, the 
installer is asked to press and hold the Reset button on the 
Sola Control to complete the safety verification session (see 
Fig. 23. Safety parameter reset.
When the Reset button is pressed and held for 3 seconds the 
confirmed safety parameters are saved in the control. The 
above Reset dialog box automatically closes when this step is 
completed.
If this step is not performed, the control remains in a safety 
lockout state until the installer resolves the unverified safety 
parameters.
Fault/Alarm Handling
Each Sola Control reports to the OI display when a safety 
lockout or an Alert occurs.
Safety lockouts are indicated on each configuration page as an 
alarm bell symbol. At the home (for S7999C) or status page 
(for S7999B), the History button turns red. If the S7999B is 
displaying the system status icons, the control in alarm will turn 
red.
The lockout history can be displayed by pressing on the 
History button. The state information about each lockout is 
displayed along with the date/time that the lockout occurred 
(see Table 3). Current date/time stamp is a display setup 
feature.
NOTE: In the event of a power interruption, the date/time 
must be reset. The OI Display does NOT have a 
backup means.
An alert log can be displayed for each control by pressing the 
Alert button on the bottom of the history status page. A 
description of the alert is displayed along with the time when 
the alert occurred (see Table 4).
History Button
The History button on the Home page serves not only as a 
button, but also displays Sola Control lockouts, holds, and 
alerts as they occur. The History button can be selected at any 
time, regardless of which type of information is displayed, to 
view history information. Pressing the History button displays a 
dialog box (see Fig. 24) that allows the user to select the type 
Table 3. Sola Control Lockout History.
Data
Comment
Lockout time
Set by display
Fault code
Unique code defining which 
lockout occurred.
Annunciator first out
First interlock in limit string 
results in a shutdown.
Description
Fault description
Burner Lockout/Hold
Source/reason for lockout/
hold
Burner control state
Sequence time
Burner control state timer at 
time of fault
Cycle
Burner control cycle
Run Hours
Burner control hours
I/O
All digital I/O status at time of 
fault
Annunciator 1-8 states
All annunciator I/O status at 
time of fault
Fault data
Fault dependent data
Table 4. Sola Control Alert Log.
Data
Comment
Alert time
Set by display
Alert code
Unique code defining which 
fault occurred.
Description
Alert description