Honeywell S7999B Manual De Usuario

Descargar
Página de 68
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
19
65-0303—05
Diagnostics Button
The Diagnostics button displays analog and digital I/O status of 
the SOLA Control. A snapshot of the diagnostic status is 
displayed and updated once per second as it changes in the 
more information about this status.
The digital I/O data is displayed as LEDs that are either on 
(green) or off (red) (See Fig. 23). Not all digital I/O can be 
displayed at the same time on the page, so a horizontal scroll 
bar is used to move the view left and right to show all digital 
I/O data.
Fig. 32. Diagnostic page (digital I/O).
The control analog I/O can also be viewed on the OI Display. A 
snapshot of the diagnostic status is displayed and updated as 
it changes in the control.
The analog I/O data is displayed as bar charts with I/O level 
represented in the I/O range (see Figure 24.) Analog I/O that is 
not enabled for the installation displays a blank I/O level. Not 
all analog I/O can be displayed at the same time on the page, 
so a horizontal scroll bar is used to move the view left and right 
to show all analog I/O status. 
Fig. 33. Diagnostics page (analog I/O). 
System Configuration 
(S7999B OI DisplayOnly)
The OI Display has some functions related to general 
configuration for the control in the end user installation.
Pressing the Display Refresh button invokes a search 
procedure (see Fig. 34). A new R7910A Hydronic Control or 
R7911 Steam Control is identified by “Unknown” status next to 
its name in the boiler system list (see Fig. 35). “Unknown” 
indicates that configuration data has not been retrieved from 
the control yet.
Fig. 34. System refresh.
Fig. 35. System configuration page.
The control connected to the Modbus network is indicated to 
the user after the search procedure has concluded.
Once the control is located it must be synchronized with the OI 
Display before it can be displayed. New controls are not 
displayed on the Home page until this synchronization (see 
below) is performed.
System Synchronization 
(S7999B OI Display Only)
The user can manually synchronize configuration data from the 
connected controls at any time.