Appendix A:  Special Requirements For Side-Wall Vented Appliances
In The Commonwealth of Massachusetts
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for 
installation of side-wall vented gas appliances as follows:
1.  For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where  
 
 
the bottom of the vent terminal and the air intake is installed below four feet above grade the following  
 
 
requirements must be satisfi ed:
 
a.  If there is not already one present, on each fl oor level where there are bedroom(s), a carbon 
 
 
monoxide detector and alarm shall be placed in the living area outside the bedroom(s).  The carbon  
 
 
 
monoxide detector shall comply with NFPA 720 (2005 Edition).
 
 
b.  A carbon monoxide detector shall be located in the room that houses the appliance or equipment
  and 
shall:
 
 
 
 
i. 
Be powered by the same electrical circuit as the appliance or equipment such that only one 
 
 
 
service switch services both the appliance and the carbon monoxide detector;
 
 
ii.  Have battery back-up power;
 
 
iii.  Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and
 
 
iv.  Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized   
 
   under 
527 
CMR.
 
c.  A product-approved vent terminal must be used, and if applicable, a product-approved air intake    
 
 
 
must be used.  Installation shall be in strict compliance with the manufacturer’s instructions.  A copy    
 
 
of the installation instructions shall remain with the appliance or equipment at the completion of the  
 
  installation.
 
d.  A metal or plastic identifi cation plate shall be mounted at the exterior of the building, four feet  
 
 
 
 
directly above the location of the vent terminal.  The plate shall be of suffi cient size to be easily read    
 
 
from a distance of eight feet away, and read “Gas Vent Directly Below”.
2.  For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where  
 
 
the bottom of the vent terminal and the air intake is installed above four feet above grade the following  
 
 
requirements must be satisfi ed:
 
a.  If there is not already one present, on each fl oor level where there are bedroom(s), a carbon 
 
 
monoxide detector and alarm shall be placed in the living area outside the bedroom(s).  The carbon  
 
 
 
monoxide detector shall comply with NFPA 720 (2005 Edition).
 
 
b.  A carbon monoxide detector shall :
 
 
 
 
i. 
Be located in the room that houses the appliance or equipment
 
 
ii.  Be either hard-wired or battery powered or both; and
 
 
iii.  Comply with NFPA 720 (2005 Edition)
 
c.  A product-approved vent terminal must be used, and if applicable, a product-approved air intake    
 
 
 
must be used.  Installation shall be in strict compliance with the manufacturer’s instructions.  A copy    
 
 
of the installation instructions shall remain with the appliance or equipment at the completion of the  
 
  installation.