IX Wiring
 
                                   
WARNING 
All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such 
requirements, with the National Electrical Code (ANSI/NFPA 70). 
 
Single Zone Wiring  
 
1)  Line Voltage (120 VAC) Connections (Fig 32) – The line voltage connections are located in the junction box under the 
R8285 fan center on the right side of the boiler. 
 
•  Black – Line voltage “hot” 
•  White – “Neutral” for boiler and circulators 
•  Green – Ground connection 
 
2)  The circulator is factory wired. If a different circulator is wired to the boiler, its full load current draw must not exceed 
12A.  
 
3)  Connect the 24-volt thermostat to terminals “R” and “G” on the R8285 fan center. Set the heat anticipator to 0.34 Amps.