Troubleshooting Chart for BSI Boilers Equipped with
Hydrolevel CG400A Low Water Cut-offs and Vent Dampers
Caution
: Read page 34 before attempting to use this chart
35
Is there an audible 
click as R8225 relay 
pulls in w hen the 
thermostat calls for 
heat?
Does relay 
pull in now ? 
Vent 
damper 
open?
START
Thermostat 
calls for heat
24 volts across 
blue and yellow  
w ires inside 
junction box?
120 volts across 
black and w hite 
transformer 
leads?
*Pow er off
*Blow n fuse or 
tripped 
breaker
*Misw ired or
loose 120  volt 
connection
N
Y
Defective 
transformer
See Note #6 on 
page 34
N
Y
Bad connection in 
thermostat w iring
Defective thermostat
Thermostat misw ired or 
misapplied 
N
N
24 volts betw een 
P2 and 2 on 
CG400 LWCO? 
Jumper missing 
betw een 1 and P1 on 
CG400
* Poor connection 
betw een transformer 
and terminals  1 & 2 on 
CG400
24 volts present 
betw een each 
pressure limit 
connection and 
yellow  transformer 
connection?
* Boiler off on pressure limit
* Defective pressure limit
Is 24 volts 
present across 
brow n and 
yellow  leads on 
R8225 relay?
Disconnect 
thermostat and 
temporarily jump 
boiler thermostat 
connections 
together 
Loose 
connection 
betw een 
transformer 
and R8225 
coil
* Defective 
R8225
See Note #7 
on page 34
Is yellow  
LED lit on 
LWCO?
* Boiler off on low  w ater
* Loose probe connection
* Poor ground path from 
heat exchanger to CG400 
case 
24 volts present 
across blue lead on 
R8225 and yellow  
transformer leads?
Defective R8225
Y
Y
N
N
Y
Y
Y
N
N
N
Y
Y
Y
N