Installation & Operation Manual
18
2  
General
 
venting   
Common venting
Crest boilers may be common vented; however, the following 
criteria MUST BE followed:
1.  Only Crest boilers may be connected to the common 
 
vent.  DO NOT mix other manufacturer’s appliances or 
 
other Lochinvar models.
2.  Crest boilers connected to the common vent must all be 
 
of the same size.
3.  Each Crest boiler must have a Lochinvar supplied flue 
 
damper installed (see Table 2D).
4.  Only vertical venting may be used when common venting 
 
Crest boilers.  Sidewall venting is not allowed.
5.  Crest boilers in a common vent must be connected and 
 
controlled with the integral Crest SMART TOUCH 
 Cascade.
 
a.  The Leader may be controlled through the Crest 
 
 
SMART TOUCH control through BMS (external 
 
 
0 - 10V signal), ModBus or its own internally 
  calculated 
set 
point.
 
b.  The Cascade (Members) must be controlled by the 
 
 
Crest Leader boiler using the efficiency optimized 
  Cascade.
For approved common vent sizing, contact the factory.
 WARNING
When Crest boilers are common vented, 
the criteria above MUST BE followed. 
Failure to follow all these requirements 
will result in severe personal injury, death, 
or substantial property damage.
Table 2D Flue Damper Kits
Flue Damper Kits
Model
Damper Size
Kit Number
FB1500
7"
DRH30000
FB2000
8"
DRH30001
FB2500
9"
DRH30002
FB3000
10"
DRH30003
FB3500
10"
DRH30003