6  
Gas connections    
Use two wrenches when tightening gas 
piping at boiler (FIG. 6-2), using one 
wrench to prevent the boiler gas line 
connection from turning.  Failure to 
support the boiler gas connection pipe 
to prevent it from turning could damage 
gas line components.
USE BACK UP WRENCH TO PREVENT
PIPE FROM ROTATING
 
Figure 6-2 Inlet Pipe with Backup Wrench
Natural gas supply pressure requirements
1.  Pressure required at the gas valve inlet pressure port:
 
• Maximum 14 inches w.c. (3.5 kPa) with no flow 
   (lockup) or with boiler on.
 
• Minimum 4 inches w.c. (.99 kPa) with gas flowing (verify 
 
  during boiler startup).
 
2.  Install 100% lockup gas pressure regulator in supply line 
if inlet pressure can exceed 14 inches w.c. (3.5 kPa) at any 
time.  Adjust lockup regulator for 14 inches w.c. (3.5 kPa) 
maximum.
Propane Gas:
Pipe sizing for propane gas
1.  Contact gas supplier to size pipes, tanks, and 100% lockup 
gas pressure regulator.
Propane Supply Pressure Requirements
1.  Adjust propane supply regulator provided by the gas 
supplier for 14 inches w.c. (3.5 kPa) maximum pressure.
2.  Pressure required at gas valve inlet pressure port:
 
• Maximum 14 inches w.c. (3.5 kPa)with no flow (lockup) 
 
  or with boiler on.
 
• Minimum 4 inches w.c. (.99 kPa) with gas flowing (verify 
 
  during boiler startup).
Maximum inlet gas pressure must not 
exceed the value specified.  Minimum 
value listed is for the purposes of input 
adjustment.
 WARNING
 WARNING
 NOTICE
 WARNING Ensure that the high gas pressure regulator 
is at least 10 feet (3 m) upstream of the 
appliance (FIG. 6-3).
Check boiler rating plate to determine which 
fuel the boiler is set for.  Crest boilers CAN 
NOT be field converted.  Failure to comply 
could result in severe personal injury, death, 
or substantial property damage.
 WARNING
Check boiler rating plate to determine 
which fuel the boiler is set for.  Crest 
boilers CANNOT be field converted. 
 
Failure to comply could result in severe 
personal injury, death, or substantial 
property damage.
Natural gas:
Pipe sizing for natural gas
1.  Refer to Table 6B for pipe length and diameter.  Based on 
rated boiler input (divide by 1,000 to obtain cubic feet per 
hour).
 
a. 
Table 6B is only for natural gas with specific gravity 
  
0.60 inches, with a pressure drop through the gas 
  
piping of 0.5 inches w.c.
 
b.  For additional gas pipe sizing information, refer to 
  
the National Fuel Gas Code, NFPA 54 / ANSI Z223.1  
  
- latest edition, or in Canada CSA B149.1 Installation 
  
Code.
 WARNING Ensure that the high gas pressure regulator 
is at least 10 feet (3 m) upstream of the 
appliance.
* GAS PRESSURE
REGULATOR
(FIELD SUPPLIED)
10'
MINIMUM
* MANUAL SHUT
OFF VALVE
(FIELD SUPPLIED)
* REQUIRED FOR INSTALLATION
IN THE COMMONWEALTH OF
MASSACHUSETTS
Figure 6-3 Gas Supply Piping to Regulator