Installation & Operation Manual
Ratings
Crest
AHRI Rating
Model Number
Note: Change “N” to 
 “L” for L.P. gas models.
Input
MBH
(Note 4)
  
 
             
       Min              Max
Gross
Output
MBH
(Note 1)
Net
AHRI
Ratings
Water,
MBH
(Note 2)
FB(N,L)1500
60
1500
1380
1200
FB(N,L)2000
80
2000
1840
1600
FB(N,L)2500
125
2500
2300
2000
FB(N,L)3000
150
3000
2760
2400
FB(N,L)3500
200*
3500
3220
2800
Other Specifications
Appliance 
Water 
Content 
Gallons
Pipe 
Size
Outlet
Pipe 
Size
Inlet
Gas Inlet 
Size
Air 
Size
Vent 
Size
(Note 3)
Weight 
w/Water
(lbs.)
96
4"
4"
1 1/2"
7"
7"
2500
132
4"
4"
1 1/2"
8"
8"
3055
161
4"
4"
2"
8"
9"
3650
181
4"
4"
2”
10"
10"
4125
215
4"
4"
2”
10"
10"
4750
Maximum allowed working pressure is located on the rating plate.
 NOTICE
Notes:
1.   The ratings are based on standard test procedures 
prescribed by the United States Department of Energy.
2.  Net AHRI ratings are based on net installed radiation of 
sufficient quantity for the requirements of the building 
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of 
1.15.  
3.  Crest boilers require special gas venting.  Use only 
the vent materials and methods specified in the Crest 
Installation and Operation Manual.  
4.  Standard Crest boilers are equipped to operate from sea 
level to 4,500 feet only with no adjustments.  
5.  High altitude Crest boilers are equipped to operate 
from 3,000 to 12,000 feet. High altitude models are 
manufactured with different control parameters for high 
altitude operation, but the sequence of operation given 
in this manual remains the same as the standard boilers.  
A high altitude label (as shown in FIG A.) is also affi xed 
to the unit.
6.  The boiler will de-rate by 4% for each 1,000 feet above 
sea level up to 4,500 feet and 4.5% for each 1,000 feet 
above 4,500 feet.
7.  Ratings have been confi rmed by the Hydronics Section 
of AHRI.
UNIT EQUIPPED FOR
HIGH ALTITUDE
3,000 FT. TO 12,000 FT.
Figure A High Altitude Label Location
*For LP models the minimum input is 420 MBH.