TABLE 7.1: SUMMARY  OF HORIZONTAL VENTING OPTIONS 
VENT OPTION #
1
2
3
CLASSIFICATION USED IN THIS 
MANUAL
HORIZONTAL 
CONCENTRIC 
HORIZONTAL
 TWIN PIPE
HORIZONTAL 
CONCENTRIC
ILLUSTRATED IN FIGURE
7.2 
7.3
7.2
VENT PIPE PENETRATION 
THROUGH STRUCTURE 
WALL
WALL
WALL
AIR INTAKE PIPE PENETRATION 
THROUGH STRUCTURE
WALL
WALL
WALL
VENT PIPE SIZE
60/100 mm
CONCENTRIC
3”
80/125 mm
CONCENTRIC
AIR INTAKE PIPE SIZE
3”
MAXIMUM  LENGTH 
VENT
BWC070
32ft
100ft
100ft
BWC090
32ft
100ft
100ft
BWC120
18ft 
100ft
100ft
BWC151
100ft
100ft
INLET
BWC070
32ft
100ft
100ft
BWC090
32ft
100ft
100ft
BWC120
18ft
100ft
100ft
BWC151
100ft
100ft
MINIMUM  LENGTH
VENT
BWC070
10in
10in
10in
BWC090
10in
10in
10in
BWC120
10in
10in
10in
BWC151
10in
10in
INLET
BWC070
10in
10in
10in
BWC090
10in
10in
10in
BWC120
10in 
10in
10in
BWC151
10in
10in
VENT TERMINAL
60/100 mm 
CONCENTRIC
CROWN 
#230511 
Crown 230531 
CONCENTRIC
or 230540
SNORKEL
AIR INTAKE TERMINAL
3” 90 ELBOW 
VENT MATERIAL
CROWN 
60/100mm 
VENT
COMPONENTS 
SHOWN IN
 TABLE 7.4a
(Note #1)
APPROVED 
STAINLESS 
STEEL VENT 
SYSTEM 
SHOWN IN 
TABLE 7.5
CROWN 
80/125mm VENT
COMPONENTS 
SHOWN IN
 TABLE 7.4b
AIR INTAKE MATERIAL
GALVANIZED 
OR PVC
    Note #1: In Vent Option #1, the 80/125mm concentric straight section (PN 230515) shown in Table 7.4a may be used between the 
boiler and the first 80/125 x 60/100 reducing elbow. If this is done, the overall maximum vent length is still restricted to that shown for 
Vent Option #1 in Table 7.1 above.
Horizontal Terminal Clearance Requirements (continued): 
•  Vent terminal must be at least 6 feet from an inside corner.
•  Under certain conditions, water in the flue gas may condense, and possibly freeze, on objects around the vent 
terminal including on the structure itself. If these objects are subject to damage by flue gas condensate, they 
should be moved or protected.
•  If possible, install the vent and air intake terminals on a wall away from the prevailing wind. Reliable operation 
of this boiler cannot be guaranteed if these terminals are subjected to winds in excess of 40 mph. 
•   Air intake terminal must not terminate in areas that might contain combustion air contaminates, such as near 
swimming pools. See Section IV for
 
more information on possible contaminates.