19
TABLE 7.9: SUMMARY  OF VERTICAL VENTING OPTIONS 
VENT OPTION #
5
6
CLASSIFICATION USED IN THIS 
MANUAL
VERTICAL
 TWIN PIPE
VERTICAL
 CONCENTRIC
ILLUSTRATED IN FIGURE
7.10
7.11
VENT PIPE PENETRATION 
THROUGH STRUCTURE
ROOF
ROOF
AIR INTAKE PIPE STRUCTURE
THROUGH STRUCTURE
ROOF
ROOF
VENT PIPE SIZE
3”
80/125 mm CONCENTRIC
AIR INTAKE PIPE SIZE
3”
MAXIMUM  LENGTH 
VENT
BWC070
98ft
95ft
BWC090
98ft
95ft
BWC120
98ft
95ft
BWC151
98ft
95ft
INLET
BWC070
98ft
95ft
BWC090
98ft
95ft
BWC120
98ft
95ft
BWC151
98ft
95ft
MINIMUM  LENGTH
VENT
BWC070
2ft
2ft
BWC090
2ft
2ft
BWC120
2ft
2ft
BWC151
2ft
2ft
INLET
BWC070
2ft
2ft
BWC090
2ft
2ft
BWC120
2ft
2ft
BWC151
2ft
2ft
VENT TERMINAL
STRAIGHT TERMINAL 
BY VENT SYSTEM MFR.
 (TABLE 7.5) 
CROWN #230532
CONCENTRIC TERMINAL 
(TABLE 7.4b)
AIR INTAKE TERMINAL
3” 180° ELBOW
(FIGURE 7.10) 
VENT MATERIAL
APPROVED STAINLESS 
STEEL VENT SYSTEM 
CROWN 80/125 mm VENT 
COMPONENTS SHOWN IN 
TABLE 7.4b
AIR INTAKE MATERIAL
GALVANIZED OR PVC
TABLE 7.8: VENT/ AIR INTAKE FITTING EQUIVALENT LENGTH
VENT FITTING
EQUIVALENT LENGTH (ft)
60/100mm 90° CONCENTRIC ELBOW
4.5
60/100mm 45° CONCENTRIC ELBOW
4.0
80/125mm 90° CONCENTRIC ELBOW
8.5
80/125mm 90° SWEEP CONCENTRIC ELBOW
5.5
80/125mm 45° CONCENTRIC ELBOW
3.0
80/125mm 90° CONCENTRIC SUPPORT ELBOW 
8.5
3” SINGLE WALL 90° ELBOW
5.5
3” SINGLE WALL 45° ELBOW
4.0