Crown Boiler BWC151 Manual De Usuario

Descargar
Página de 81
71
B.  Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will  
 
shut down and the display will alternate between the number “9” and the letter “b” followed by a two digit  
 
service code.  The boiler will automatically restart once the condition that caused the lockout is corrected.
CODE
CONDITION
POSSIBLE CAUSES 
b 08
Pressure switch circuit open.
• Blockage in intake or vent system. 
• Vent and/or intake system not constructed in accordance 
with Part VII. 
• Blocked or leaking pressure switch tubing.
• Heat exchanger or burner blockage. 
• Terminals exposed to high winds.
• Blockage in condensate trap above vent.
b 18
MCBA supply sensor detected temperatures in excess 
of 200°F.
•  Heating  load  at  time  of  error  was  far  below  the  minimum                  
firing rate of the boiler.
• Defective primary pump or no flow in primary loop (Piping 
Method 1).
• Control system miswired so that boiler operation is 
permitted when no zones are calling. 
b 19
MCBA return sensor detected temperatures in excess of 
200°F.
 
• See possible causes for “b18”.
• Flow through boiler reversed.
• Sensor wiring reversed.
b 24
MCBA is reading a return sensor temperature higher 
than the supply sensor temperature. Condition must be 
present for at least 75s for this error code to appear. 
• Flow through boiler reversed. Verify correct piping and 
pump orientation.
• No boiler water flow. Verify that system is purged of air 
and that appropriate valves are open. 
• Sensor wiring reversed.
• Supply or return sensor defective. 
b 25
Supply water temperature has risen too quickly.
• See possible causes for “b18”.
• Inadequate boiler water flow. Verify that pump is 
operating and that pump and piping are sized per Part IX 
of this manual. 
b 26
Boiler safety limit, or external limit wired across terminals 
3&4, is open.
• See possible causes for “b18”.
• Defective supply sensor.
b 30
Temperature rise between supply and return is too high.
• Inadequate boiler water flow. Verify that pump is 
operating and that pump and piping are sized per Part IX 
of this manual. 
b 61
Pressure switch circuit closed with fan off.
• Blockage in pressure switch hose. 
• Pressure switch wires shorted together.
• Defective pressure switch.
• Loose or miswired fan speed harness (if “b61” error code 
is observed while fan is running). 
b 65
Fan is not achieving set point speed.
• Loose or incorrect fan speed control connection.
• Defective fan.
Table 14.3:  Soft Lockout Codes Displayed