Pressure Testing Burner System Gas 
Connections
 
 
1.  Open equipment shutoff valve (see 
Figure 33 page 16). 
2.  Open propane/LP supply tank valve 
for propane/LP burner system or main 
gas valve located on or near gas meter 
for natural gas burner system. 
3.  Make sure control knob of burner 
system is in the OFF position. 
4.  Check all joints from equipment 
shutoff valve to thermostat gas valve 
(see Figure 34 for propane/LP or 
Figure 35 for natural). Apply 
commercial leak test solution to all gas 
joints. Bubbles forming show a leak. 
Correct al leaks at once. 
5.  Light burner system (see Operating 
Stove with Burner System, pages 21 
through 22). Check all other internal 
joints for leaks. 
 
Equipment Shutoff Valve 
Propane /LP Supply 
Tank 
Gas Valve Location 
Figure 34– Checking Gas Joints for Propane/LP Gas Burner System 
CONTROL VALVE LOCATION 
EQUIPMENT 
SHUTOFF 
VALVE 
GAS  METER 
Figure 35– Checking Gas Joints for Natural Gas Burner System  
 