Power up and Testing 
Problem Solving 
Troubleshooting 
The following illustration shows the front panel of the 
unit and the controls used during installation. 
The table after this paragraph provides corrective action 
for possible trouble situations. If further assistance is 
required, please contact a Crestron customer service 
representative.  
Front Panel Controls and Indicators 
 
CLS-C6RF/C6MRF Installation Troubleshooting 
TROUBLE 
POSSIBLE 
CAUSE(S) 
CORRECTIVE ACTION 
Unit is not 
receiving 
line power. 
Verify that the unit is properly 
connected to the power line and 
that the circuit breaker is 
closed. 
Unit does not 
function. 
Loads are 
not 
connected. 
Verify that the loads are 
operational and that they are 
connected to the iLux unit. 
Loads turn on 
and off, but do 
not dim. 
Wrong load 
type 
settings. 
Correct load type settings. * 
Lights flicker 
at low levels 
Incorrect 
low-end 
limit setting. 
Change low-end limit setting. * 
Verify the basic installation and wiring connections as 
follows: 
1. Press 
the 
Lights button to enable manual light 
control, and press the right side and the left side 
of each of the function buttons to increase and 
decrease the lighting level of those loads. Verify 
that the intended loads and corresponding LED 
bargraphs respond appropriately. 
* Refer to the latest version of the Crestron CLS-C6RF iLux Integrated 
Lighting System w/infiNET Operations Guide (Doc. 6418), for details 
on setting load types and low-end limits. 
Further Inquiries 
2. Press 
the 
OFF button to turn off all loads. The 
loads will ramp down to off while the two-digit 
display counts down to off (blank). Two seconds 
after all lights have turned off, the unit’s master 
air-gap relay opens making it safe to service the 
lighting installations.  
If you cannot locate specific information or have 
questions after reviewing this guide, please take 
advantage of Crestron's award winning customer service 
team by calling Crestron at 1-888-CRESTRON  
[1-888-273-7876].  
 
You can also log onto the online help section of the 
Crestron website (
) to ask 
questions about Crestron products. First-time users will 
need to establish a user account to fully benefit from all 
available features. 
 
 
 
 
Future Updates 
 
As Crestron improves functions, adds new features, and 
extends the capabilities of the CLS-C6RF and the  
CLS-C6MRF, additional information may be made 
available as manual updates. These updates are solely 
electronic and serve as intermediary supplements prior to 
the release of a complete technical documentation 
revision.  
 
 
 
 
 
Check the Crestron website periodically for manual 
update availability and its relevance. Updates are 
identified as an “Addendum” in the Download column. 
 
 
4  
 iLux
 Integrated Lighting Systems w/infiNET
:  CLS-C6RF & CLS-C6MRF 
Installation Guide – DOC. 6416A