Crestron electronic 277 Volt Manual De Usuario

Descargar
Página de 16
CRESTRON GREEN LIGHT™ 
Architectural Dimming 
Load Wiring (Section B) 
CAUTION:  Bypass jumpers are provided on each output to allow testing and to protect the module during 
installation. The jumper shorts the LSW and DM terminals so that the load circuit is energized when the branch 
breaker is on. Do not remove the bypass jumper until all feed and load wiring has been completed, and the circuits 
have been tested for electrical faults. 
NOTE:  Use copper conductors only – rated 75
°C. 
Wire Gauge and Torque Values 
TERMINAL 
CONNECTOR MAX WIRE RANGE 
TORQUE 
STRIP LENGTH 
LOAD & DM OUTPUTS 
26-10 AWG 
5.31 lb-in (0.6 Nm) to 
7.08 lb-in (0.8 Nm) max 
3/8” 
(9 mm) 
DIM CONTROL  
(GLX-DIMFLV8 only) 
28-12 AWG 
4.43 lb-in 
(0.5 Nm) 
5/16” 
(8 mm) 
GROUND BAR 
14-10 AWG 
35 lb-in 
(4.0 Nm) 
5/16” 
(8 mm) 
GROUND LUG 
14-4 AWG 
45-25 lb-in 
(5.1-2.8 Nm) 
3/4" 
(19 mm) 
1.  Each output has a label with the number of the controlling circuit breaker printed on it. With the 
corresponding circuit breaker turned off, connect the controlled circuit (LOAD) wires to the output per the 
markings on the module as shown in the following diagrams. Terminals for load wiring accept one 10 – 14 
AWG wire.  
Load Wiring for GLX-DIM6, GLX-DIMFLV8, and GLX-HSW8 (Jumper Installed) 
TO BRANCH BREAKER
(PREWIRED)
TO NEUTRAL BUS
(PREWIRED)
TO LOAD
JUMPER
(INSTALLED)
GLX-DIM6
GLX-HSW8 AND GLX-DIMFLV8
TO BRANCH BREAKER
(PREWIRED)
TO LOAD
TO NEUTRAL BUS
(PREWIRED)
TO LOAD
(3-WIRE BALLASTS
ONLY)
JUMPER
(INSTALLED)
 
Installation Guide – DOC. 6688A 
CRESTRON GREEN LIGHT Architectural Dimming  