Abbreviation
Definition
Abbreviation
Definition
FRQNCY, FREQ,
FREQUENCY
Frequency
SYS, SYSTM
System
FUNC
Function
T, TRBL, TRB, TROUB
Trouble
GRND
Ground
TST
Test
HI
High
VER
Version
HSTRY
History
W, WFLW, WTF
Waterflow
INIT
Initialize
ZN, ZON
Zone
IP
Internet Protocol address
 
Table 10.1: Abbreviations on control panel display
Appendix B: Control Panel Display Descriptions
The meanings of control panel messages are given in the following table:
FPD-7024 Panel Display
Message
Panel Display Message Definition
FIRE DIRTY PT XX
A smoke detector with the Chamber Check feature indicates a dirty
chamber.
FIRE DSBL PT
Fire point is disabled from the keypad.
FIRE TRBL PT XXX
Trouble condition for specific points on the system. Check control
panel wiring and field wiring for shorts or opens. Also check point
programming to ensure the control panel knows what points belong
on the system.
FIRE TROUBLE
General fire zone trouble message. Refer to the second line of
display for more information.
INST FLT 4Z EXP
There is a missing FPD-7034 Four Zone Expander Board, or the
expander appeared unexpectedly since the last time the system
was powered.
INST FLT MX EXP
There is a missing D7039 MUX Expander Module, or the expander
appeared unexpectedly since the last time the system was
powered.
MONI DSBL PT
Monitor point is disabled from the keypad.
MONI TRBL PT XXX
Trouble with a monitor point occurred.
MUX BUS A FAILURE
MUX BUS B FAILURE
A wiring problem on Bus A or Bus B in Class B mode occurred.
Check the wiring for shorts or opens.
MUX CPU FAILURE
A CPU failure on the D7039 Expander Board occurred. Ensure that
the D7039 is correctly installed on the header pins. If the message
persists, call for service immediately.
SUPV DSBL PT
Supervisory point is disabled from the keypad.
SUPV TRBL PT XXX
Trouble with a supervisory point occurred.