Receiver output
PHONE 2 RESTORE
55
dd/dd tt:tt ql ACCT aaaa PHONE RESTORAL
+++ ACCT aaaa PHONE LINE=2
SYSTEM TROUBLE
56
dd/dd tt:tt ql ACCT aaaa EQUIPMENT FAIL
+++ ACCT aaaa SDI=001 COND=ccc
SYSTEM TROUBLE RESTORE
57
dd/dd tt:tt ql ACCT aaaa EQUIP RESTORAL
+++ ACCT aaaa SDI=001 COND=ccc
MANUAL TEST
58
dd/dd tt:tt ql ACCT aaaa TEST REPORT
DATA LOST
59
dd/dd tt:tt ql ACCT aaaa COMM FAIL
+++ ACCT aaaa PHONE#=1
EEPROM FAILURE
60
dd/dd tt:tt ql ACCT aaaa EQUIPMENT FAIL
+++ ACCT aaaa SDI=001 COND=18
EEPROM RESTORAL
61
dd/dd tt:tt ql ACCT aaaa EQUIP RESTORAL
+++ ACCT aaaa SDI=001 COND=18
SMOKE POWER FAULT
62
dd/dd tt:tt ql ACCT aaaa EQUIPMENT FAIL
+++ ACCT aaaa SDI=001 COND=3
SMOKE POWER RESTORE
63
dd/dd tt:tt ql ACCT aaaa EQUIP RESTORAL
+++ ACCT aaaa SDI=001 COND=3
REMOTE PROGRAMMING FAIL
66
dd/dd tt:tt ql ACCT aaaa RAM ACCESS FAIL
REMOTE PROGRAMMING SUCCESS
67
dd/dd tt:tt ql ACCT aaaa RAM ACCESS OK
Notes:
dd/dd tt:tt: date and time
aaaa: account number
ccc: numeric identifier
uuu: user ID
zzz: point
Table 10.4: Modem 111a
2
 reporting
The following table provides event numbers and their condition as they appear in the history
log.
Condition
System
event
Condition
System
event
Option bus device at address 1 failed
2
Remote relay module 2 disabled by
user
52
Option bus device at address 2 failed
3
Class A, Style  6 wiring failure on MUX
bus
53
Option bus device at address 3 failed
4
MUX bus A (9-128) failed
54
Option bus device at address 4 failed
5
MUX bus B (129-255) failed
55
Option bus device at address 5 failed
6
MUX module processor failure
56
Option bus device at address 6 failed
7
Remote NAC module 1, output 1 wiring
fault
57
 
108 en | Appendices
Fire Alarm Control Panels
2012.08 | 04 | F01U008458
Installation and Operation Manual
Bosch Security System, Inc.