2500 Operating Manual 
 
 
1-2
1.3 Specifications 
1.3.1 Electrical 
specifications 
 
Primary (AC) power: 
Accessory (battery) voltage 
120VAC, 60 Hz, 1.5A max 
24VDC; (charging current, 1.0A) 
Control Unit Requirements: 
Standby current 
 
Alarm current 
 
110mA, 24VDC (not including auxiliary devices and 
modules) 200mA, 24VDC (not including auxiliary devices 
and modules) 
Output Ratings: 
 
System alarm contacts 
 
System trouble contacts  
 
4-wire smoke detector power 
 Auxiliary 
power 
 
 
 
Max ripple voltage 
 
SPDT, 2A, 30VDC, 0.6 power factor 
SPDT, 2A, 30VDC, 0.6 power factor  
24VDC, .5A power limited, regulated, resetable*** 
24VDC, .5A power limited, regulated, resistive load, non-
resetable*** 
500mV (4-wire smoke and aux. power circuits) 
Optional Accessories: 
 
Remote annunciator RALCD 
 
Max number per panel 
 
Style Z  (Class A) Module (CAM) 
 ZDACT 
 
Power limited,100mA, 24VDC per unit, (see Appendix A) 

0mA standby, 25mA alarm (see Appendix A) 
90mA max in alarm (See Appendix A) 
Notification Appliance Circuit (Bells): ** 
 Current, 
nominal 
 
Max short circuit current 
 
Normal supervisory current
 
End of line resistance 
 
24VDC, 2.0A (max) ***, power limited 
2.5A, power limited 
2.7mA 
5.1K ohms 
Initiating Device Circuits (Zones): 
 Smoke 
capacity 
(24VDC)† 
 Standby 
voltage 
 
 
Max ripple voltage 
 
Max short circuit current 
Normal standby current 
 
Alarm current threshold 
Max impedance for alarm 
End of line resistance 
Max. line resistance 
 
25 detectors, 0.1mA type; 20 detectors, 0.12mA type 
27.5 VDC (max) to 16 VDC (min) 
500mV 
60mA, power limited 
4.5mA 
approx. 20mA 
1.5K ohms 
5.1K ohms 
100 ohms 
Supervisory Initiating Circuit:†† 
 Max 
voltage 
 
Max short circuit current 
 
Max circuit resistance 
 
Normal supervisory current 
 
 Trouble 
current 
 
End of line resistance   
 
27.5 VDC 
10mA, power limited 
100 ohms 
3.5mA 
2mA (low trouble) 5mA (supervisory)  
5.1K ohms  
Reverse Polarity Outputs:†††   Max 
voltage   
Max line current  
 
24 VDC 
15mA 

* All terminals are capable of up to #12 AWG wire. 
** Use any UL listed polarized notification appliances rated 24VDC. 
***Total system current for auxiliary device powered by the panel not to exceed 2.5 amps. This includes NAC power, auxiliary 
power, reverse polarity outputs, four wire detector power, and remote annunciator. The latter three are 0.5A max combined. 
† Max load: 2.5mA. Use only detectors that are listed in compatibility list. 
†† Use supervisory devices with normally open contacts. 
††† Power limited
 
1.3.2 Housing 
•  Type  18-gauge sheet steel with hinged, removable, locked door.