AGM300 / ADM800 Refrigerant Gas Leak Monitor Mechanical Room Placement 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The ADM800 should be mounted outside of the mechanical room or at least just inside of a door to the room. 
This is the “split architecture design” for safety of the operator. The ADM800 can be located up to 4500 feet 
from the AGM300. The ADM800 is the main interface by which you program the AGM300, acknowledge 
alarms, and observe conditions inside of the mechanical room. Note that there are two additional alarm relay 
contacts in the ADM800 that can be programmed to alarm with “leak, spill, evacuate, fault or monitor on”. 
 
 
AGM300 
Ammonia 
Gas 
Monitor 
Outside Hallway
Machine Room 
Sample Inlet Pickup Points 
Chiller 
Sample Inlet 
Pickup Point 
Aux. Horn/Strobe 
Remote Alarm
Fresh air purge 
from area away 
from ammonia 
gas 
Exhaust Fan 
ADM800 
Ammonia Display 
Module outside of 
mechanical room