Honeywell 5820XL Manual De Usuario

Descargar
Página de 228
System Operation
151209
8-9
8.5.16 Communicating with a Remote Computer
An installer at the panel site can initiate communications between the panel and a computer 
running the SKSS 5660. You can use this feature to upload a panel configuration. For 
example, if you have made programming changes to an installation on site using an 
annunciator, you can send your changes to the computer, so that the central station will have 
the latest data about the installation. See the software manual for more information (PN 
151240).
To initiate communication:
1. From the Main Menu, select 
 for Up/Download.
2. From the next screen that displays, select the communication device. Options are:
3. If you are using the panel’s internal modem to communicate, you will be prompted to 
enter a phone number. If you are communicating via the RS232 connection, a phone num-
ber is not needed and this step will be skipped.
If the phone number you will be calling is already displayed, press 
. Continue with 
Step 4.
If the phone number you will be calling is not already displayed, enter the number and press 
. A phone number can be up to 40 digits long and can contain the following special 
characters.
Use the number buttons on the annunciator or the up- and down-arrow keys to select special 
characters. Characters begin displaying after “9”.
4. You will be prompted to enter an account number. If the account number you want to use 
is already displayed, just press 
 to begin communication. 
If the account number displayed is not the correct one, enter the account number and press 
 to begin communication. 
5. The panel will attempt to communicate with the computer. If communication was estab-
lished, the upload task you created will be placed in the SKSS 5660 job queue, awaiting 
processing. When processing is completed, an “Unsolicited Upload” task will appear in 
the queue.
 = Internal Modem
If you select this option, you will use the panel’s built-in modem to call 
the panel.
 = RS232 connection
If you select this option, the panel and a computer are both on-site 
connected via a 9-pin straight-through serial cable. 
#
Pound (or number) key on the telephone
*
Star key on the telephone
,
Comma (character for 2-second pause)
9
1
2
ENTER
ENTER
ENTER
ENTER