IntelliKnight 5820XL Installation Manual
8-14
151209
8.7
Releasing Operations
This control panel supports two types of releasing, Double Interlock Zone, and Single 
Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the 
system, and the Single Interlock does not. An interlock switch is typically a dry-contact 
pressure switch.
When a Single or Double Interlock Zone releasing is selected the system is will automatically 
default the following system parameters:
Note: The defaults created can be modified through programming if desired.
Output Group 2 is created. Output Group 2 will be defaulted as an "Alarm" output group 
for all releasing zones. NAC [34:001] is assigned to Output Group 2.
Output Group 3 is created. Output Group 3 will be defaulted as an "Pre-Alert" output 
group for all releasing zones. NAC [34:002] is assigned to Output Group 3.
Output Group 4 is created. Output Group 4 will be defaulted as a "Release" output group 
for all releasing zones. NAC circuit [34:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches, or inter-
lock/pressure switches.
Figure 8-5  Wiring Configuration for Solenoid
Do not mix cross alarming zones with smoke verification zones. There must be at least two 
automatic detection devices in each protected space. Spacing must be reduced to 0.7 times the 
linear spacing in accordance with NFPA 72. See Section 7.4 for zone option programming.
Table 8-2: Approved Releasing Solenoids
Manufacturer
Part Number
Rating
Current
Freq
Asco
T8210A107
24 VDC
3A max
0 Hz
8210G207
24 VDC
3A max
0 Hz
Model 7641
Must Mounted
at the Solenoid