10-1
Section 10
Testing and Troubleshooting
10.1 Troubleshooting
This section of the manual offers suggestions for troubleshooting hardware problems. Please 
read this section if you encounter a problem when installing the control panel. If these 
suggestions do not solve your problem or if you encounter a problem that is not listed here, 
contact Silent Knight Technical Support at 800-446-6444 for assistance.
10.2 Common Problems
Problem
Possible Cause / Suggested Actions
Trouble message "DBL ADDR" (Double 
Address) displays on LCD.
An address has been assigned to more than one detector. Correct the address 
following the procedure described in Section 5.8.
Auxiliary power or notification circuits 
have incorrect polarity.
Correct polarity. For notification and auxiliary power circuits: When in alarm 
or powered, terminals labeled "X" are positive, terminals labeled "O" are 
negative. 
SLC devices are not being recognized 
(trouble message "Missing" displays). 
Check hardware connections. 
If devices are physically connected, make sure wiring is correct (see Section 
5.4). For the main panel, the positive side of device must be connected to 
terminal 34; the negative side must be connected to Terminal 33. For 5815XL 
devices, make sure the device connects to the 5815XL via the SLC OUT 
terminals. 
There can be only one SLC loop on the main panel and on each 5815XL 
module. Do not connect devices to terminals labeled SLC IN.
Make sure SLC devices have been addressed properly following the 
procedure described in Section 5.8. 
For contact monitor modules, which are addressed using dip switches, the dip 
switch must be set to the correct address before power is applied to the SLC 
loop. If this procedure is not followed, the device will have an incorrect 
address.
Make sure correct polarity has been observed for SLC device wiring. See 
Section 5.4.