Honeywell 5820XL Manual De Usuario

Descargar
Página de 228
151209
3-1
Section 3
Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth 
installation. Please read this section thoroughly, especially if you are installing a 5820XL 
panel for the first time.
3.1
What’s in the Box?
The IntelliKnight 5820XL ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Two keys for user operation of the on-board annunciator (installer operations require the 
Installer’s Code)
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series
3.2
Environmental Specifications
It is important to protect the 5820XL control panel from water. To prevent water damage, the 
following conditions should be AVOIDED when installing the units:
Intended for indoor use in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production 
machinery)
When selecting a location to mount the 5820XL control panel, the unit should be mounted 
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or 
humidity not exceeding 93% noncondensing.