Honeywell 5820XL Manual De Usuario

Descargar
Página de 228
IntelliKnight 5820XL Installation Manual
4-4
151209
4.3.1
RBB Accessory Cabinet
The Model RBB Accessory cabinet can be used when your backup batteries requirements use 
backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet 
holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 
cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries
To properly install  the accessory cabinet and backup batteries, follow these steps:
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch ply-
wood. This is necessary because the weight of the batteries inside the accessory cabi-
net could cause the cabinet to pull away from the drywall.
When mounting on concrete, especially when moisture is expected, attach a piece of 
3/4-inch plywood to the concrete surface and then attach the RBB cabinet to the ply-
wood.
If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no 
more than 18" away from the main control panel cabinet. This will ensure that the bat-
tery cables reach the battery terminals.
Figure 4-3  RBB Cabinet Mounting Holes
2. Connect the main control panel battery cables to the battery cable extenders as shown in 
Figure 4-4  Splicing Control panel Battery Cable to RBB Battery Cable Extenders
Cabinet