4.13 Flexputs
 
I/O Circuits
The six Flexput™ circuits are an innovative and versatile feature of the control panel. They 
can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 
wire detectors), or as auxiliary power (resettable, continuous, or door holder).
The polarity of the Flexput terminals differs depending on whether the circuit is programmed 
as an input or and output circuit. If the circuit is programmed as an input circuit (for a detector 
or normally open contact) the X terminal is negative and O terminal is positive. If the circuit is 
programmed as an output circuit (Aux power or NAC) then the X terminal is positive and the 
O terminal is negative.
This section of the manual explains how to install conventional notification appliances and 
initiating devices to be used with the system.
4.13.1 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for 
Class A (Style Z) and Class B (Style Y) configurations.
4.13.1.1 Regulated Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the 
back of this manual.
To install a circuit:
1. Wire Class B Notification appliances as shown in Figure 4-30.