Control Panel Installation
151209
4-33
4.13.2 Conventional Input Switch Circuits
This section of the manual explains how to install conventional initiating devices for Class A 
(Style D) or Class B (Style B) configurations.
4.13.2.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations, 
directly to the Flexput circuits of the control panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 4-32.
2. Configure the circuit through programming (see Section 7.6).
Figure 4-32  Class B Input Switches
UL Listed EOL
Model 7628
4.7 k
Ω
Supervised
Power Limited