Control Panel Installation
151209
4-47
4.15.6 Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the 
5820XL FACP dry contacts. The FACP contacts must be supervised by the remote station 
transmitter module using end-of-line resistors (ELRs) with a value determined by the 
transmitter manufacturer. Power is also provided by the remote station transmitter 
manufacturer. Refer to the remote station transmitter manufacturer’s manual for details.