DUCT SMOKE DETECTOR
WiRiNg DiAgRAMS
(PRIMARY)
L2
WHITE
SWITCHING DEVICE
  (BY OTHERS)
L1
(OVERRIDE)
BROW
N
BLAC
K
ORANG
E
BLUE
BLAC
K
DH100ACDCLP DUCT DETECTOR
115 VAC
RED
TOR
15
5
12
11
2
1
14
13
3 4
18
8
16 17
6 7
19 20
9 10
C
A B
YELLOW
YELLOW
YELLOW
YELLOW
SWITCH #1
SWITCH #2
DH100ACDCLP DUCT DETECTOR
BLUE
RED
WHITE
24 VAC/VDC
WHITE
12
11
14
13
1 2 3 4 5
15
18
16 17
19 20
8
6 7
9 10
C
A B
RED
RED
E/P SWITCH
OPTIONAL
THIRD E/P SWITCH
OPTIONAL
SECOND E/P SWITCH
RED
RED
WHITE
E/P SWITCH
RED
WHITE
E/P SWITCH
RED
BLAC
K
BLAC
K
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE 
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF 
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
C
A
9 10
B
7 8
5 6
3 4
1 2
20
17 18
15 16
13 14
11 12
19
WHITE
RED
BLUE
220/240 VAC 
DH100ACDCLP DUCT DETECTOR
TOR w/ EP Switch
Copyright © 2008 Greenheck Fan Corporation
DH100 Smoke Detector Rev. 6 May 2008