Architectural and Engineering
Specifications
     The smoke alarm shall be Kidde model KN-SMFM-i or approved equal. It 
shall be powered by a 120VAC, 60Hz source along with a rechargeable bat-
tery backup. The unit shall incorporate an ionization sensor with nominal sen-
sitivity of .50 to .98%ft. The temperature operation range shall be between   
40˚F and 100˚F (4.4˚C and 37.8˚C) and the humidity operating range shall be 
up to 85% relative humidity.
 
The smoke alarm can be installed in standard junction boxes listed   
below.  The electrical connection (to the alarm) shall be made with a plug-in 
connector. A maximum of 24 Kidde devices can be interconnected in a mul-
tiple station arrangement. The interconnect system must not exceed the NFPA 
(National Fire Protection Association) limit of 18 initiation devices, of which 
12 can be smoke alarms. With 18 initiating devices (smoke, heat, CO, etc.),
interconnected, it is still possible to interconnect 6 strobe lights and or   
relay modules. 
 
The alarm shall include a test button that will electronically simulate   
the presence of smoke and cause the unit to go into alarm. This sequence 
tests the unit’s electronics, battery and horn to ensure proper operation.
 
The unit shall include a piezoelectric horn that is rated at 85 decibels   
at 10 feet. Single button operates both Smart Hush™ and alarm test for easy opera-
tion and less confusion. The unit shall also include a low battery warning utiliz-
ing a brief alarm chirp every 60 seconds for a minimum of seven (7) days.
 
The unit shall incorporate red and green LED indicators. The green LED 
indicates the status of the alarm. The red LED is a visual indicator of alarm 
and warning chirps. 
 
Standby Condition: The green LED will be lit if on AC power or blink 
once every 30 seconds if on battery backup. 
Alarm Condition: When the 
alarm senses products of combustion and enters alarm the red LED will   
blink in unison with the sounder and the green LED will flash once every   
2 seconds. The flashing LEDs and pulsating alarm will continue until the air 
is cleared. When the units are interconnected, only the green LED of the 
alarm(s) sensing smoke or is being tested (the originating unit) will flash.   
All other units in the interconneced system will sound an alarm and flash the 
red LED but the green LED will remain at is standby state.
 Alarm Memory:   
This smoke alarm is equipped with an alarm memory, which provides a visual 
indication when an alarm has been activated. The green LED will flash every 
16 seconds to indicate the memory condition. 
Smart Hush
TM
 Mode:  The 
green LED will flash every 3 seconds but the alarm will not make any sound, 
indicating the smoke alarm is in the Smart Hush
TM
 Mode. 
 
The unit shall at a minimum meet the requirements of UL217, NFPA72, 
(chapter 11), The State of California Fire Marshall, NFPA 101 (One and
two family dwellings) Federal Housing Authority (FHA), Housing and Urban
Development (HUD). It shall also include a 10-year manufacture’s limited warranty.
Innovative low profile alarm fits in most common electrical 2-gang and   
plastic, round boxes with 3 1/2” hole spacing. Depth of box must exceed   
2 1/8”. Unit will displace 7.5 cubic inches.
Width of screw posts
must not exceed .45”
120V AC/DC Wire-in Low Profile Smoke Alarm
Sealed Rechargeable Battery Backup
Part Number 21007288
Model KN-SMFM-i
Installation of Smoke Alarm
The smoke alarm must be installed to comply with all local codes having jurisdiction 
in your area. All wiring shall be in accordance with articles 210 and 300.3(B) of
the US National Electrical Code, ANSI / NFPA 70 and NFPA 72. The multiple station 
interconnect wiring must be in the same raceway as the AC power wiring. In addi-
tion the resistance if the interconnect wiring shall be a maximum of 10 ohms. 
Make certain all alarms are wired to a single, continuous (non-switched) power 
line, which is not protected by a ground fault interrupter. A maximum of 1000 ft. 
of wire can be used in the interconnect system. Use standard UL listed household 
wire as required by code.
Ordering Information
Install Options
Distributed by:
Technical Specifications
Model: 
KN-SMFM-i
UPC: 
0-47871-07288-0
Power Source: 
120VAC (80mA) with Rechargeable Battery Back Up
Sensor: 
Ionization
Audio Alarm:
85dB at 10ft
Temperature Range:  40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range:
up to 85% relative humidity (RH)
Size: 
5.25” width  x 1.5” depth x (.5”installed)
Weight: 
.5lb
Interconnects: 
Up to 24 Kidde devices/18 initiating
Wiring: 
Quick-connect plug with 6” pigtails
LED: 
Red, visual alarm indicator
 
Green, current state indicator
Warranty: 
10 year limited
*Not for sale by individual unit      
Ordering  
 
 
 
Dimensions 
 
Case/ 
Layers/  
Skid 
Number 
UPC 
I2F5 
Pack Quantity 
(w x d x h inches) 
Weight  Skid 
Skid 
Weight 
21007288 
0-47871-07288-0  100-47871-07288-7 
Cut Case (4 units)  6.5 x 13.25 x 6 
 3 lbs 
 75 
  4 
230 lbs
P/N: KL-SIL-SM sheet  
rev. 01-2009
Square Box
Octagon Box
Round Box
2 Gang Box