Model IFT9701 Transmitter Instruction Manual
Remotely Mounting the Transmitter
 continued
3.4
Connecting the transmitter to the sensor
To connect the transmitter to the sensor:
Micro Motion 9-wire cable is required. See Section 3.4.1 for information on cable types 
offered by Micro Motion.
Depending on your cable type, you must either install the cable in conduit or use cable glands. 
See Section 3.4.2 for information on conduit installations. See Section 3.4.3 for information 
on cable gland installations.
For information on connecting the wires to the terminals, see Section 3.4.4.
Micro Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide, shipped with the cable, 
provides additional information on cable types, cable preparation, and installation requirements.
3.4.1
Cable types
Micro Motion supplies 9-wire jacketed, shielded, or armored cable.
Jacketed cable is CE-compliant when it is installed inside user-supplied sealed metallic 
conduit that provides 360° termination shielding for the enclosed cable. See Figure 3-4 for an 
illustration of jacketed cable.
Shielded and armored cable are CE-compliant when the cable is installed with the 
factory-supplied cable glands. See Figure 3-5 for an illustration of shielded cable, and 
Figure 3-6 for an illustration of armored cable.
Each cable type is available with a PVC or Teflon
®
 FEP jacket. For temperature ranges of 
cable jacket materials, see Table 3-1.
See Table 3-2 for guidelines on cable selection. All cable types are acceptable for cable tray 
installation.
CAUTION
Improper installation of cable, cable gland, or conduit 
could cause inaccurate measurements or flowmeter 
failure.
To ensure 360° termination shielding for flowmeter wiring, 
install the factory-supplied cable gland or user-supplied 
sealed metallic conduit to the conduit opening on the 
sensor junction box.
Figure 3-4
Jacketed cable
Jacket 
material
Outside 
diameter
Minimum bend radii
Static 
(no load) 
condition
Under 
dynamic 
load
inches (mm)
inches (mm)
inches (mm)
PVC
0.415 (10)
3 1/8 (80)
6 1/4 (159)
Teflon
®
 
FEP
0.340 (9)
2 5/8 (67)
5 1/8 (131)
Jacket
Drain wire (4)
Foil shield (4)
Filler (5)