Model IFT9701 Transmitter Instruction Manual
Configuration with a HART Communicator
 continued
6.2.6
Range values for milliamp output
Range values are the flow rates represented by the milliamp output at 4 mA and at 20 mA.
To set range values, use the menu below and follow these steps:
1. At the online menu, choose 3 (basic setup).
2. At the basic setup menu, choose 3 (analog range values).
3. Choose the upper or lower range value for setting.
To set the upper range value, which is the flow rate represented by the output at 20 mA, 
choose 1 (primary variable upper range value), or 
To set the lower range value, which is the flow rate represented by the output at 4 mA, 
choose 2 (primary variable lower range value).
4. Enter the desired range value, then press F4 (enter).
5. To send the range values to the flowmeter, press F2 (send).
6.2.7
Pulse output scaling
The pulse output produces a frequency proportional to the flow rate. Pulse output scaling requires 
entry of frequency and flow rate values.
To scale the pulse output, use the menu below and follow these steps:
1. At the online menu, choose 3 (basic setup).
2. At the basic setup menu, choose 4 (frequency factor).
3. Enter a value for the frequency in pulses per second (Hertz) that corresponds to the maximum 
flow rate, then press F4 (enter).
4. When the HART Communicator display returns to the basic setup menu, choose 5 (rate 
factor).
5. Enter the maximum value of the flow rate, then press F4 (enter). The entered value 
corresponds to the frequency that was entered in Step 3.
6. To send the pulse output scaling to the flowmeter, press F2 (send).
1 Process variables
2 Diag/service
3 BASIC SETUP
4 Detailed setup
5 Review
1 Tag
2 PV  unit
3 ANALOG RANGE VALS
4 Freq factr
5 Rate factr
1 PV  URV
2 PV  LRV
1 Tag
2 PV  unit
3 Analog range vals
4 FREQ FACTR
5 RATE FACTR
1 Process variables
2 Diag/service
3 BASIC SETUP
4 Detailed setup
5 Review