continued
Table 32
Non-Critical Status Diagnostic Message Table, continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
Possible Cause
What to Do
2-1
Excess Zero Correct
PV1
Or
Zero Correction is Out of
Limits
STATUS TAG ID.#
EX. ZERO COR PV1
EX. ZERO COR PV1
ZERO correction factor is outside
acceptable limits for PV1 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.
acceptable limits for PV1 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.
•
Verify calibration.
•
If error persists, call the
Solutions Support Center
Solutions Support Center
4-1
Excess Zero Correct
PV2
STATUS TAG ID.#
EX. ZERO COR PV2
EX. ZERO COR PV2
ZERO correction factor is outside
acceptable limits for PV2 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.
acceptable limits for PV2 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.
•
Verify calibration.
•
If error persists, call the
Solutions Support Center
Solutions Support Center
8-1
Excess Zero Correct
PV3
STATUS TAG ID.#
EX. ZERO COR PV3
EX. ZERO COR PV3
ZERO correction factor is outside
acceptable limits for PV3 range.
acceptable limits for PV3 range.
•
Verify calibration.
•
If error persists, call the
Solutions Support Center
Solutions Support Center
9-1
Excess Zero Correct
PV4
STATUS TAG ID.#
EX. ZERO COR PV4
EX. ZERO COR PV4
ZERO correction factor is outside
acceptable limits for PV4 range.
acceptable limits for PV4 range.
•
Verify calibration.
•
If error persists, call the
Solutions Support Center
Solutions Support Center
9-5
In Cutoff PV4
STATUS TAG ID.#
IN CUTOFF PV4
IN CUTOFF PV4
Calculated flow rate is within
configured low and high limits for
PV4 low flow cutoff.
configured low and high limits for
PV4 low flow cutoff.
Nothing – wait for flow rate to
exceed configured high limit.
exceed configured high limit.
Verify that flow rate is in cutoff.
5-4
Input Mode PV1 (DP)
STATUS TAG ID.#
INPUT MODE PV1
INPUT MODE PV1
Transmitter is simulating input for
PV1.
PV1.
Exit Input mode:
SCT – Press “Clear Input Mode”
button on the DP InCal tab.
SFC – Press [
SHIFT
], [
INPUT
], and
[
CLR
] keys.