Honeywell SMV 3000 Manual De Usuario

Descargar
Página de 217
134
SMV 3000 Transmitter User’s Manual 
1/99
11.4
Diagnostic Messages,  
Continued
Diagnostic Messages,
continued
Table 34
Informational Status Message Table
SMV Status
SCT Status Message SFC Display Message TDC Status Message
Possible Cause
What to Do
6-3
2 Wire TC PV3
STATUS  TAG ID.
2 WIRE TC PV3
2 WIRE TC PV3
PV3 input is being provided by
2-wire Thermocouple (T/C) type.
Nothing – Information only. However,
this may indicate a problem if sensor
type does not match the sensor
physically connected to transmitter.
6-0
2 Wire RTD PV3
STATUS  TAG ID.
2 WIRE RTD PV3
2 WIRE RTD PV3
PV3 input is being provided by
2-wire RTD type.
Nothing – Information only. However,
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
6-1
3 Wire RTD PV3
STATUS  TAG ID.
3 WIRE RTD PV3
3 WIRE RTD PV3
PV3 input is being provided by
3-wire RTD type.
Nothing – Information only. However,
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
6-2
4 Wire RTD PV3
STATUS  TAG ID.
4 WIRE RTD PV3
4 WIRE RTD PV3
PV3 input is being provided by
4-wire RTD type.
Nothing – Information only. However,
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
4-3
PV2 Sensor = AP
-
STATUS 4-3
Sensor type for the current SMV
is absolute pressure.
Nothing – Information only.
4-4
PV2 Sensor = GP
-
STATUS 4-4
Sensor type for the current SMV
is gauge pressure.
Nothing – Information only.
-
Write Protected
URV 1 . TAG ID.
 WRITE PROTECTED
-
The value could not be written
because the transmitter is write
protected.
The hardware jumper within the
device must be repositioned in order
to permit write operations.