SMV 3000 Transmitter User’s Manual
1/99
11.4
Diagnostic Messages,
Continued
Diagnostic Messages,
continued
continued
Table 34
Informational Status Message Table
SMV Status
SCT Status Message SFC Display Message TDC Status Message
Possible Cause
What to Do
6-3
2 Wire TC PV3
STATUS TAG ID.
2 WIRE TC PV3
2 WIRE TC PV3
PV3 input is being provided by
2-wire Thermocouple (T/C) type.
2-wire Thermocouple (T/C) type.
Nothing – Information only. However,
this may indicate a problem if sensor
type does not match the sensor
physically connected to transmitter.
this may indicate a problem if sensor
type does not match the sensor
physically connected to transmitter.
6-0
2 Wire RTD PV3
STATUS TAG ID.
2 WIRE RTD PV3
2 WIRE RTD PV3
PV3 input is being provided by
2-wire RTD type.
2-wire RTD type.
Nothing – Information only. However,
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
6-1
3 Wire RTD PV3
STATUS TAG ID.
3 WIRE RTD PV3
3 WIRE RTD PV3
PV3 input is being provided by
3-wire RTD type.
3-wire RTD type.
Nothing – Information only. However,
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
6-2
4 Wire RTD PV3
STATUS TAG ID.
4 WIRE RTD PV3
4 WIRE RTD PV3
PV3 input is being provided by
4-wire RTD type.
4-wire RTD type.
Nothing – Information only. However,
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
this may indicate a problem if number
of wires displayed does not match
number of RTD leads physically
connected to transmitter; or if sensor
type should be thermocouple.
4-3
PV2 Sensor = AP
-
STATUS 4-3
Sensor type for the current SMV
is absolute pressure.
is absolute pressure.
Nothing – Information only.
4-4
PV2 Sensor = GP
-
STATUS 4-4
Sensor type for the current SMV
is gauge pressure.
is gauge pressure.
Nothing – Information only.
-
Write Protected
URV 1 . TAG ID.
WRITE PROTECTED
-
The value could not be written
because the transmitter is write
protected.
because the transmitter is write
protected.
The hardware jumper within the
device must be repositioned in order
to permit write operations.
device must be repositioned in order
to permit write operations.