Sears 153.33262 Manual De Usuario

Descargar
Página de 44
18
12” Max.
Permanent
openings to 
the outside or
additional 
rooms within 
the building
Closet
or other
confined
space
12” Max.
FIGURE 13.
All Air from the Building                                   
When additional air is to be provided to the confined area 
from additional room(s) within the building, the total volume of 
the room(s) must be of sufficient size to properly provide the 
necessary amount of fresh air to the water heater and other 
gas utilization equipment in the area. If you are unsure that the 
structure meets this requirement, contact your local gas utility 
company or other qualified agency for a safety inspection. 
Each of the two openings shall have a minimum free area of 1 
square inch per 1,000 BTUH of the total input rating of all gas 
utilization equipment in the confined area, but not less than 100 
square inches (Figure 14).
FIGURE 14.
All Air from Outdoors                                            
Outdoor fresh air can be provided to a confined area either 
directly or by the use of vertical and horizontal ducts. The fresh 
air can be taken from the outdoors or from crawl or attic spaces 
that freely communicate with the outdoors. Attic or crawl spaces 
cannot be closed and must be properly ventilated to the outside. 
Ductwork must be of the same cross-sectional area as the 
free area of the opening to which they connect. The minimum 
dimension of rectangular air ducts cannot be less than three 
inches. 
The size of each of the two openings is determined by the 
method in which the air is to be provided. Refer to Table 4 to 
calculate the minimum free area for each opening. Figures 15, 
16, 17 and 18 are typical examples of each method. 
Louvers and Grilles                                               
In calculating free area for ventilation and combustion air supply 
openings, consideration must be given to the blocking effect 
of protection louvers, grilles, and screens. These devices can 
reduce airflow, which in turn may require larger openings to 
achieve the required minimum free area. Screens must not be 
smaller than 1/4” mesh. If the free area through a particular 
design of louver or grille is known, it should be used in calculating 
the specified free area of the opening. If the design and free area 
are not known, it can be assumed that most wood louvers will 
allow 20 - 25% of free area while metal louvers and grilles will 
allow 60 - 75% of free area. 
Louvers and grilles must be locked open or interconnected with 
the equipment so that they are opened automatically during 
equipment operation. 
Keep louvers and grilles clean and free of debris or other 
obstructions.
TABLE 4
Minimum Free Area of Permanent Openings for Ventilation and 
Combustion Air Supply - All Air from Outdoors Only.
Based on total BTUH input rating for all utilizing equipment 
within the confi ned space.
Opening Source
Minimum Free Area 
Per Opening (sq. in.)
Reference Drawing
*Direct to outdoors
1 sq. in, per 4000 BTUH
Figure 15
Vertical Ducts
1 sq. in, per 4000 BTUH
Figure 16
Horizontal Ducts
1 sq. in, per 2000 BTUH
Figure 17
Single Opening
1 sq. in, per 3000 BTUH
Figure 18
Example: A water heater with an input rating of 50,000 BTUH using 
horizontal ducts would require each opening to have a minimum free 
area of 25 square inches.
Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.
These openings connect directly with the outdoors through a venti-
lated attic, a ventilated crawl space, or through an outside wall.
Consult the local codes of your area for specific ventilation and 
combustion air requirements.
 
Confined
Space
Permanent
Openings
1 Square 
inch/1000
BTUH
(min. 100
sq. in.)