Wiring diagram 
Air supply flap 
~ 230 V 
Power supply 
400V / max.16A 
Fan motor 
2-speed / 400V 
Thermal 
contact 
motor 
Frost 
protection 
thermostat 
Night 
thermostat 
Day 
thermostat 
If several fans are operated simultaneously up to a 
total capacity of max. 4 kW, the connection is made 
via an external terminal distributor! 
If several fans are operated simultane-
ously, connect all thermal contacts in a 
row! 
SW 2.2 DSK switching unit 
 
Rotary current 400 volt, fan 2-speed  
maximum electrical capacity 4 kW 
Wall-mounted, full motor protection through integrated 
connections for thermal contacts, connection terminals 
for thermal contacts, room thermostats, frost protection 
thermostat and mixed-air box adjustment motor. 
Design 
Plastic housing, protection type IP 65. 
Protective insulation in accordance with VDE, front 
plate with symbols for switching positions and operating 
modes, power input and protective conductor terminals, 
main contactor, speed selector with the functions 
“Speed 1 / Speed 2“, control fuse, operating and mal-
function lights, operating mode switch with the functions 
“Off / Release / Thermostat / Continuous Operation”, 
control relay, terminals for the motor output, connection 
terminals for the thermal contacts, room thermostats, 
frost protection thermostats, mixed-air adjustment motor 
and flap positioning switch. 
Functionality 
The mixed-air box can be controlled by means of a flap 
positioning switch. If the ventilation is shut off, the flaps 
are automatically set to “Closed”. 
  
The frost protection thermostat closes the flaps 
switches the fan off. 
Switching on again after a problem 
Each time the power supply is interrupted or the fan 
malfunctions, the operating mode switch has to be reset 
to “0/Release”! 
Group switching 
The switching unit is suitable for group switching. Sev-
eral motors wired the same way can be connected to 
one switching unit. 
The total capacity of the connected motors may not ex-
ceed the permissible switch capacity of the switching 
unit. The thermal contacts of all motors are to be con-
nected in a row. 
Important information about safe operation 
Grounding and earthing or protective wiring and fuse 
protection must be done
 
by the customer in accordance 
with the requirements of the VDE as well as the respon-
sible EVU. 
The electrical unit connections must be performed by 
authorised personnel in the line with the valid require-
ments in compliance with local laws and in accordance 
with the wiring diagrams. 
Thermal 
protection for 2 
units 
Thermal 
protection for 3 
units 
Thermal 
protection for 4 
units 
Wiring diagram of the thermal contacts