Pressure Testing Gas Supply Piping System 
Test Pressures In Excess Of 
1
/
2
 PSIG (3.5 kPa)
1.   Disconnect appliance with its appliance main gas valve 
(control  valve)  and  equipment  shutoff  valve  from  gas 
supply piping system. Pressures in excess of 
1
/
2
 psig will 
damage heater regulator.
2.   Cap  off  open  end  of  gas  pipe  where  equipment  shutoff 
valve was connected.
3.   Pressurize supply piping system by either using compressed 
air or opening propane/LP supply tank valve.
4.   Check all joints of gas supply piping system. Apply mixture 
of liquid soap and water to gas joints. Bubbles forming 
show a leak.
5.   Correct all leaks at once.
6.   Reconnect fireplace and equipment shutoff valve to gas 
supply. Check reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 
PSIG (3.5 kPa)
1.   Close equipment shutoff valve (see Figure 15).
2.   Pressurize supply piping system by either using compressed air or 
opening propane/LP supply tank valve.
3.   Check all joints from propane/LP supply tank to equipment shutoff 
valve (see Figure 15). Apply mixture of liquid soap and water to gas 
joints. Bubbles forming show a leak.
4.   Correct all leaks at once.
Pressure testing heater gas connections 
1.   Open equipment shutoff valve (see Figure 15).
2.   Open propane/LP supply tank valve.
3.   Make sure control knob of heater is in the OFF position.
4.   Check all joints from equipment shutoff valve to thermostat gas 
valve (see Figure 16). Apply mixture of liquid soap and water to 
gas joints. Bubbles forming show a leak.
5.   Correct all leaks at once.
6.   Light heater (see Operating Heater, pages 19 through 21). Check 
all other internal joints for leaks.
7.   Turn off heater (see “To Turn Off Gas to Heater,” page 19.
8.   Replace front panel. 
CHECKING GAS CONNECTIONS 
INSTALLATION
Test  all  gas  piping  and  connections 
for leaks after installing or servicing. 
Correct all leaks at once.
W
ARNING
Never  use  an  open  flame  to  check 
for  a  leak. Apply  a  mixture  of  liquid 
soap and water to all joints. Bubbles 
forming show a leak. Correct all leaks 
at once.