THE ROUND® CREATIVE SERIES Y460A2003 THERMOSTAT
69-1358
4
— Let the system operate through the ammeter for 
at least one minute before taking a reading. 
Record the reading here ______________ .
— Reconnect the W wire to the W terminal.
Move the heat anticipator indicator to match the 
number you recorded in Step 3 or in Step 7.
NOTE:  Hot water and steam systems require you to 
multiply the current rating times 1.3. For elec-
tric heat systems, add the fan relay current, 
usually 0.2A to 0.4A.
Snap the cover ring over the thermostat dial.
8 SET THE TEMPERATURE
Turn the transparent dial until the desired point on 
the setting scale is aligned with the pointer, as shown 
in the illustration.
IMPORTANT:
During a call for heat or cool, an electrical 
spark can be seen through the colored 
decorator cover ring. Do not be alarmed; 
this is normal operation for a mercury 
switch. 
Set Subbase Switch
CAUTION
Equipment Damage Hazard.
Can cause permanent damage to the 
compressor.
Do not rotate the thermostat dial back and forth 
just to observe the electrical spark; observe the 
compressor five-minute minimal-off period.
To operate the heating system, set the subbase 
System switch to Heat. To operate the cooling 
system, set the subbase System switch to Cool. Set 
it to Off if you want neither heating or cooling.
Set the Fan switch to On for continuous fan 
operation or to Auto for fan operation during heating 
or cooling cycles.
9 CHECK OUT THE SYSTEM
Heating
Turn down the temperature setting to the lowest 
point. Move the System switch to Heat. Raise the 
temperature setting above room temperature; the 
heating equipment should start. Lower the 
temperature setting below room temperature; the 
heating system should stop.
Cooling
CAUTION
Equipment Damage Hazard.
Can cause permanent damage to the 
compressor or other equipment.
To avoid possible compressor damage, allow 
the compressor to remain off for five minutes 
before restarting.
To avoid possible equipment damage, do not 
operate cooling when the outside temperature is 
below 50
°
F (10
°
C).
See equipment manufacturer instructions.
CAUTION
Equipment Damage Hazard.
Can cause permanent damage to the 
compressor.
Do not rotate the thermostat dial back and forth 
just to observe the electrical spark; observe the 
compressor five-minute minimal-off period.
Turn up the temperature setting to the highest point. 
Move the subbase System switch to Cool. Lower the 
temperature setting below the room temperature; the 
cooling equipment should start. Raise the tempera-
ture setting above the room temperature; the cooling 
system should stop.
WARRANTY
Honeywell warrants this product, excluding battery, to be free 
from defects in the workmanship or materials, under normal 
use and service, for a period of one (1) year from the date of 
purchase by the consumer. If, at any time during the warranty 
period, the product is defective or malfunctions, Honeywell 
shall repair or replace it (at Honeywell’s option) within a rea-
sonable period of time.
If the product is defective,
i.
return it, with a bill of sale or other dated proof of pur-
chase, to the retailer from which you purchased it, or
ii.
package it carefully, along with proof of purchase 
(including date of purchase) and a short description of 
the malfunction, and mail it, postage prepaid, to the fol-
lowing address:
Honeywell Inc.
Return Goods Department
1050 Berkshire Lane
Plymouth, MN 55441-4437
This warranty does not cover removal or reinstallation costs. 
This warranty shall not apply if it is shown by Honeywell that 
the defect or malfunction was caused by damage which 
occurred while the product was in the possession of a 
consumer.
THERMOMETER
TEMPERATURE 
SETTING
M13419
50
60
70
80
50
60
70
80