 Temporary timer for extended presence or absence 
The Comfort and Economy modes can be temporarily extended
 
by 0.5 to 9.5 hours using the temporary 
timer. 
 
 
 
1.  To set the temporary timer, press and hold the operating mode button for maximum 3 seconds.
While   holding the button, turn the rotary knob clockwise or counterclockwise as required. 
a)  Turn the rotary knob clockwise to extend Comfort mode. 
Display:   
   0....+9:30 
b)  Turn the rotary knob counterclockwise to extend Economy mode.  
Display:    
  0....-9:30 
2.  Release the operating mode button and the mode is temporarily changed, indicated by    . 
After the temporary timer has elapsed, the thermostat will resume operation in the operating mode 
that was active before: 
Extended Comfort mode 
 
New operating mode = Economy 
Extended Economy mode 
 
New operating mode = Comfort 
  If Economy cannot be selected via the operating mode button (P02≠2), Protection mode will be 
used for extended absence instead! 
  The temporary timer function is aborted whenever a new setting is made 
 
 Note: 
 Extended Comfort mode is also possible when an external contact such as a keycard switch or central time clock is active
 To enable this function, the time for the extended period must be set via parameter P68. 
 
 Changing from heating to cooling mode
 
 
 
 
 
  Depending on the type of plant, the changeover from heating to cooling (or vice 
versa) is made either automatically by a changeover sensor or a remote change-
over switch, or manually by pressing the operating mode button (see parameter 
P01) 
  To select cooling or heating manually (P01=2), press the operating mode button 
until the desired mode appears 
  With automatic changeover or continuous heating / cooling, symbols   / 
indicate that the system currently operates in heating or cooling mode 
  With manual changeover, symbol   appears, indicating that the system currently 
operates in heating or cooling mode  
 Control parameters 
 
 
 
If you want to change control parameters, proceed as follows: 
1.   Press both buttons simultaneously for at least 3 seconds. 
2.   Release them and, within 2 seconds, press the right button again for 3 seconds.  
The display shows P01. 
3.   Select the required parameter by turning the rotary knob. 
4.   Press button   (OK). The current value of the selected parameter starts blinking and can be
changed by turning the rotary knob. 
5.  Press button    (OK) to confirm the adjusted value, or     (Esc) to cancel the change.  
If you wish to adjust additional parameters, repeat steps 3 through 5, or press   (Esc) to leave the 
parameter setting mode. 
 
 Parameter list 
 
No.     Parameter name 
 
Default value 
Setting range 
Adj. 
P01    Control sequence                              2-pipe / 2-
stage: 
1 = cooling only 
 
4-pipe: 
4 = H and C           
0 = heating only 
1 = cooling only 
2 = H/C changeover, manually 
3 = H/C changeover, auto 
4 = heating and cooling 
 
P02 
Mode selection via operating 
mode button 
 
1 = Comfort / Protection mode 
2 = Comfort / Economy /  
       Protection mode  
 
P03 
Mode selection via fan mode 
button 
0 = Auto / Manual 
1 = Manual 
2 = Auto / Manual /  
       Protection mode 
 
P04 
Selection of °C or °F 
0 = °C 
1 = °F 
 
P05 
Sensor calibration 
0.0 K 
– 3…3 K 
 
P06 
Standard temperature display 
0 = Room temperature 
1 = Setpoint 
 
P07 
Additional display information 
0 = --- (no display) 
1 = ˚C and ˚F 
 
P08 
Comfort basic setpoint 
21 °C 
5…40 °C 
 
P09 
Minimum setpoint limitation in 
Comfort mode  
5 °C 
5…40 °C 
 
P10 
Maximum setpoint limitation in 
Comfort mode   
35 °C 
5…40 °C 
 
P11 
Setpoint for heating in Economy 
mode  (WheatEco) 
15 °C 
OFF, 5 °C…WcoolEco 
 
P12 
Setpoint for cooling in Economy 
mode  (WcoolEco) 
30 °C 
OFF, WheatEco…40°C 
 
P13 
Electric heater in cooling mode 
ON 
OFF = Disabled  
ON  = Enabled 
 
P14 
Button lock 
0 = Disabled 
1 = Automatic 
2 = Manual  
 
P15 
Fan speed in dead zone  
(Comfort mode) 
0 = Disabled 
1 = Stage 1 (H or C) 
2 = Stage 1 (Cooling only) 
 
 
The control parameters displayed depend on the DIP switch settings made 