SPECIAL FEATURES 
Page 15 
FORCED AIR COOLING 
Certain regulators may be equipped for forced-air cooling and 
include fans mounted on the radiators. The fans are usually 
automatically controlled by means of the change in oil 
temperature (see Connection Diagram). The thermometer 
located in the top transformer oil contains two identical 
switches which control fan operation when fan control switch is 
in “Auto” position.
 
SUBBASE ASSEMBLY 
                                                                                                      
Subbase assemblies are available in 4-inch high increments 
from 21 through 49 inches for most JFR regulators. The 
proper height is selected by picking the elevation that will 
provide required clearance from foundation to the live part of 
the regulator bushing.
 
 
 
The switches are normally set to start the fans at 65°C and to 
stop them at 55°C top oil temperature, but may be adjusted 
plus or minus 5°C.  
A thermal overload relay is mounted on each fan motor. Any 
fan that develops trouble will be automatically disconnected 
from the line without affecting the other fans of the system. 
One fan can be removed from the radiators without affecting 
the operation of the others. When fans are out of service, 
care must be exercised to prevent overloading the regulator.