INTRODUCTION  
 
Page 3   
 
 
PHYSICAL CONSIDERATIONS 
•  Handling. Type JFR regulators are designed to be lifted 
either by a forklift at the base or by use of lifting hooks 
on the side of each tank. Each JFR regulator is provided 
with either 2 or 4 lifting hooks on the side of each tank. 
The number of hooks has been established to provide a 
margin of safety.  Use all supplied lifting hooks when 
lifting. 
 
•  Location. Type JFR regulators are designed for outdoor 
installation. Any regulator may be platform or pedestal 
mounted. Regulators provided with hanger brackets are 
suitable for pole mounting. When the regulator is to be 
installed in a substation on a pedestal it is recom-
mended that a minimum elevation to the live connection 
be established, as required by applicable codes. 
 
 
Elevation. When the regulator will be used at an elevation 
above 1000 meters (3300 feet) the kVA rating must be de-
rated per ANSI C57.15 to assure operating temperature 
limits are not exceeded. 
LINE TERMINALS AND 
CONNECTIONS 
Type JFR voltage regulators are routinely equipped with line 
bushing terminals per the following criteria. 
 
 
Nameplate Line Current 
Rating 
Conductor Size Range
or Threaded Stud Size 
50A to 300A 
#2 to 477 MCM 
301A to 668A 
#2 to 800 MCM 
669A to 1200A 
1.125- 12 UNF-2A 
1201 A to 2000A
1.500- 12 UNF-2A
 
Clamp type terminals for use through 668 ampere are 
capable of accepting an aluminum or copper conductor. 
Tank grounding provision consists of a 0.5-13NC tapped 
hole in a steel pad for regulators rated to 300 amperes. 
Above 300 ampere ratings, a stainless steel pad with two 
0.5-13NC tapped holes is provided. 
ELECTRICAL CONSIDERATIONS 
Type JFR regulators are commonly installed using any of 
four electrical configurations. 
• One regulator in single-phase application. (Figure 4A) 
• Three regulators in wye on a grounded-neutral three-
phase system. (Figure 4D) 
• Two regulators in open delta on a three-phase 
ungrounded system. (Figure 4B) 
• Three regulators in closed delta on a three-phase 
ungrounded system. (Figure 4C) 
Each of the four alternatives, when complete with switching 
provisions, will take the electrical configuration as shown 
on the next page. 
The descriptions 'S', 'L', and 'SL' are embossed into the cover 
for user convenience at time of installation. 
Improper use of lifting provisions can cause death, 
serious injury, or equipment damage.  
 
To prevent: 
 
Do not use cover lifting eyes to lift complete unit. 
Cover lifting eyes are for untanking only.
 
 
 
 
WARNING
 
 
 
 
 
Hazardous voltage present at the line terminals of the 
bushings on the cover of the regulator. 
Will cause serious injury or death. 
To prevent: 
De-energize the regulator before servicing.